OMRON provides a range of Analog Timers and Digital Timers, as well as Time Switches for 24-hour, weekly, or annual time control.

Introduction Features
Principles Classifications
Engineering Data Further Information
Explanation of Terms Troubleshooting

Related Contents

Primary Contents



Symbols Used in Internal Connection Diagram

NameSymbolDescription
Symbol used
in catalogs
Symbol defined
by JIS
NO contacts
Normally open contacts (A pair of contacts which are normally open when no relay input is applied.)
NC contacts
Normally closed contacts (A pair of contacts which are normally closed when no relay input is applied.)
Transfer
contacts
Transfer contacts (NO and NC contacts that have a common contact terminal are collectively called "transfer contacts".)
The contacts shown in A and B are all transfer contacts. The NC contact is either on the right side or on the upper side.
Time-limit
operating
contacts
A: NO contacts
B: NC contacts
Time-limit
resetting
contacts
A: NO contacts
B: NC contacts
Time-limit
operation,
timelimit
resetting
contacts
A: NO contacts
B: NC contacts
Manually
operated,
automatic
resetting
contact
Contacts that reset when the operator releases their hand. These contacts are used, for example, to operate a pushbutton switch. (Same for pushbutton, pull, and rotating switches.)
A: NO contacts
B: NC contacts
Synchron
ous motor
A miniature motor which operates in synchronization with the power supply frequency.
Relay
An electromagnetic relay
LED
Used to indicate the operating status of the Timer.

[[Inrush Currents for Timers and Time Switches]]

"---" indicates a constant current and therefore the corresponding values are omitted from the table. All the values are approximate values and should therefore only be used as a guide.

Timers (Major Models)

Model or seriesVoltageApplied voltageInrush current
(peak value)
Time (see note) *
H3AM-NS/-NSR100 to 240 VAC264 VAC2.74 A1.7 ms
H3CA-A series24 to 240 VAC or 12 to 240 VDC264 VAC1.6 A0.6 ms
H3CA-8/-8-306200/220/240 VAC264 VAC1.5 A0.6 ms
100/110/120 VAC132 VAC780 mA5 ms
24 VDC------
H3CA-8H/-8H-306200/220/240 VAC264 VAC1.6 A1.6 ms
100/110/120 VAC132 VAC1.5 A5 ms
24 VDC26.4 VDC1.2 A2 ms
H3CR-A/-A8/-AP100 to 240 VAC or264 VAC780 mA1.8 ms
137.5 VDC310 mA3.2 ms
24 to 48 VAC or26.4 VAC830 mA2.4 ms
26.4 VDC570 mA6.3 ms
H3CR-A8E100 to 240 VAC or264 VAC1.76 A0.1 ms
137.5 VDC550 mA0.2 ms
24 to 48 VAC/DC26.4 VAC270 mA35 ms
26.4 VDC270 mA31 ms
H3CR-AS/-A8S24 to 48 VAC or 12 to 48 VDC26.4 VAC370 mA2.2 ms
26.4 VDC250 mA3.2 ms
H3CR-F100 to 240 VAC or264 VAC750 mA1 ms
137.5 VDC0.5 A9.1 ms
24 to 48 VAC or26.4 VAC0.83 A10 ms
26.4 VDC0.57 A9.4 ms
H3CR-HS
series
100/110/120 VAC132 VAC1.05 A111 ms
200/220/240 VAC264 VAC1.07 A119 ms
24 VAC/DC26.4 VAC1.26 A133 ms
26.4 VDC0.85 A137 ms
48 VDC52.8 VDC0.73 A112 ms
100 to 125 VDC137.5 VDC0.62 A109 ms
M
series
100/110/120 VAC132 VAC1.02 A364 ms
200/220/240 VAC264 VAC1.03 A323 ms
24 VAC/DC26.4 VAC1.21 A478 ms
26.4 VDC0.87 A560 ms
48 VDC52.8 VDC0.71 A384 ms
100 to 125 VDC137.5 VDC0.62 A380 ms
H3DE-MS/F/G24 to 230 VAC/DC253 VAC4.4 A0.03 ms
253 VDC2.68 A0.03 ms
26.4 VDC203 mA11 ms
H3DE-H200 to 230 VAC200 VACApprox. 0.8 A130 ms
100 to 120 VAC100 VACApprox. 0.93 A130 ms
48 VAC/DC48 VACApprox. 0.95 A130 ms
48 VDCApprox. 0.68 A70 ms
24 VAC/DC24 VACApprox. 1.25 A140 ms
24 VDCApprox. 0.89 A40 ms
H3DK-M/S/F/G24 to 240 VAC/DC264 VACApprox. 4.69 A46.27 ms
24 VDCApprox. 0.168 A134 ms
264 VDCApprox. 3.64 A46 ms
12 VDC13.2 VDCApprox. 2.62 A418.67 ms
H3DK-H100 to 120 VAC132AApprox. 2.06 A1320 μs
200 to 240 VAC264 VACApprox. 2.38 A677.33μs
24 to 48 VAC/DC52.8 VACApprox. 1.81 A1810 μs
24 VACApprox. 1.68 A19.8 ms
24 VDCApprox. 1.16 A35.2 ms
52.8 VDCApprox. 2.44 A8.84 ms
H3DS24 to 230 VAC or 24 to 48 VDC253 VAC3 A1 ms
26.4 VDC0.5 A4 ms
H3DT-N/L/A/F/G24 to 240 VAC/DC264 VAC7.04 A500 μs
24 VDC336 mA5.36 ms
264 VDC4.92 A704 μs
H3DT-H100 to 120 VAC132 VAC2.08 A21.6 μs
200 to 240 VAC264 VAC4.08 A23.2 μs
24 to 48 VAC/DC52.8 VAC1.09 A19.2 μs
24 VDC668 mA63.2 ms
52.8 VDC1.96 A15.2 ms
H3FA-A24 VDC26.4 VDC1.8 A0.01 ms
12 VDC13.2 VDC1.5 A0.01 ms
6 VDC6.6 VDC1.1 A0.05 ms
5 VDC5.5 VDC1.1 A0.05 ms
H3FA-SA24 VDC26.2 VDC1.8 A0.01 ms
12 VDC13.2 VDC1.5 A0.01 ms
6 VDC6.6 VDC1.1 A0.05 ms
5 VDC5.5 VDC1.1 A0.05 ms
H3M series200/220/240 VAC264 VAC1.2 A0.5 ms
100/110/120 VAC132 VAC620 mA0.4 ms
110 VDC------
100 VDC------
48 VDC52.8 VDC5 A1 ms
24 VDC26.4 VDC2.6 A1 ms
12 VDC13.2 VDC1.3 A1 ms
H3RN seriesAll specifications except for 24 VAC------
24 VAC26.4 VAC200 mA3 ms
H3Y seriesAll specifications except for 12 VDC------
12 VDC13.2 VDC350 mA0.4 ms
H3YN seriesAll specifications except for 12 VDC------
12 VDC13.2 VDC600 mA1 ms
H5AN series100 to 240 VAC264 VAC23 A1 ms
100 VDC110 VDC8 A2 ms
12 to 24 V DC26.4 VDC15 A6.5 ms
H5CN series100 to 240 VAC264 VAC800 mA1 ms
12 to 48 VDC52.8 VDC400 mA1 ms
H5CX-A[]-N series100 to 240 VAC264 VAC4.8 A0.5 ms
H5CX-A[]D-N24 VAC or 12 to 24 VDC26.4 VAC9.5 A1 ms
26.4 VDC6.6 A1 ms
H5CX-L[]-N series100 to 240 VAC264 VAC5.3 A0.4 ms
24 VAC or 12 to 25 VDC26.4 VAC6.4 A1.4 ms
26.4 VDC4.4 A1.7 ms
H5CX-B[]-N series12 to 24 VDC26.4 VDC4.4 A1.7 ms
H5CX-A/-L series
(previous models)
100 to 240 VAC264 VAC5.3 A0.4 ms
24 VAC or 12 to 24 VDC26.4 VAC6.4 A1.4 ms
26.4 VDC4.4 A1.7 ms
H5CX-B series
(previous models)
12 to 24 V DC26.4 VDC6 A1.2 ms
H5CZ series100 to 240 VAC264 VAC4.6 A0.4 ms
24 VAC or 12 to 24 VDC26.4 VAC9.5 A1 ms
26.4 VDC6.6 A1 ms

Time Switches (Major Models)

Model or seriesVoltageApplied voltageInrush current
(peak value)
Time (see note) *
H4KV-DSA-R100 to 200 VAC240 VAC4.8 A1.1 ms
H4KV-DSA
(previous models)
100 to 200 VAC240 VAC0.7 A0.5 ms
H5L-AAll specifications------
H5S-W series100 to 240 VAC264 VAC3.1 A0.2 ms
24 VDC26.4 VDC1.3 A2.7 ms
H5S-Y series100 to 240 VAC264 VAC3.1 A0.2 ms
24 VDC26.4 VDC1.4 A2.7 ms
H5S series100 to 240 VAC264 VAC2.5 A0.3 ms
24 VDC26.4 VDC1.1 A3 ms
H5F series100 to 240 VAC264 VAC2 A0.3 ms

* The time of the inrush current is measured in the range shown in the following waveform.