Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

M22N

Indicators

M22N

22-mm dia. Indicators. Control panel miniaturization through a more compact design and modified wiring direction. Addition of Push-In Plus terminal blocks for easy wiring.

about this Product Family

Certified Standard Ratings

UL508 (File No.E76675), CSA C22.2 No.14

12 mA 6 VAC/DC
12 mA 12 VAC/DC
12 mA 24 VAC/DC
12 mA 100-120 VAC
12 mA 200-240 VAC

TÜV (EN60947-5-1)

80 mA 6 VAC/DC
40 mA 12 VAC/DC
20 mA 24 VAC/DC
10 mA 100-120 VAC
5 mA 200-240 VAC

CCC (GB14048.5)

6, 12, 24 VAC/DC
100-120, 200-240 VAC

Application Standards

UL1059 and UL486E (Push-In Plus terminal block type)

Ratings

LED Lamps

Rated voltage Operating voltage Current
6 VAC/DC 6 VAC/DC ±10% Approx. 11 mA (red, orange, yellow, or blue)
Approx. 5 mA (white or green)
12 VAC/DC 12 VAC/DC ±10% Approx. 12 mA (red, orange, yellow, or blue)
Approx. 5 mA (white or green)
24 VAC/DC 24 VAC/DC ±10% Approx. 12 mA (red, orange, yellow, or blue)
Approx. 5 mA (white or green)
100 VAC 100 VAC ±10% Approx. 12 mA (red, orange, yellow, or blue)
Approx. 5 mA (white or green)
110 VAC 110 VAC ±10%
120 VAC 100-130 VAC
200 VAC 200 VAC ±10% Approx. 12 mA (red, orange, yellow, or blue)
Approx. 5 mA (white or green)
220 VAC 220 VAC ±10%
230 VAC 230 VAC ±10%
240 VAC 220-250 VAC

Characteristics

Item Indicator
Allowable operating
frequency
Mechanical --
Electrical --
Insulation resistance --
Contact resistance --
Dielectric strength Between terminals
of same polarity
--
Between each terminal
and ground
2,500 VAC at 50/60 Hz for 1 min. (initial value)
Vibration resistance Malfunction 10 to 55 Hz, 1.5-mm double amplitude
Shock resistance Malfunction 1,000 m/s2 max.
Durability Mechanical --
Electrical --
Ambient operating temperature*1 -25 to 55°C
Ambient operating humidity 35% to 85% RH
Ambient storage temperature*1 -40 to 80°C
Degree of protection*2 Conforming to IP66, NEMA 4X, NEMA13
Electric shock protection class Class II
PTI (tracking characteristic) 175
Degree of contamination
(application environment)
3 (EN 60947-5-1)
Weight Approx. 30 g

*1. With no icing or condensation.
*2. Degree of protection from the front of the panel.