Input specification | 100 to 240 V input | |||
---|---|---|---|---|
Power ratings *1 | 15 W | 35 W | ||
Efficiency | 68% min. | 73% min. | ||
Input | Voltage *2 | 100 to 240 VAC (allowable range: 85 to 264 VAC, 80 to 370 VDC *9) | ||
Frequency *2 | 50/60 Hz (47 to 450 Hz) | |||
Current
*3 |
100 V input | 0.4 A max. | 1 A max. | |
200 V input | 0.25 A max. | 0.6 A max. | ||
Harmonic current emissions | --- | |||
Leakage
current *3 |
100 V input | 0.5 mA max. | ||
200 V input | 1 mA max. | |||
Inrush
current (for a cold start at 25 °C) *3 |
100 V input | 20 A max. | ||
200 V input | 40 A max. | |||
Output
*4 |
Voltage adjustment range *5 | - 10% to 15% (with V. ADJ) (48-V models: ± 10%) | ||
Ripple *3 | 2% (p-p) max. | |||
Input variation influence | 0.4% max. with AC input voltage | |||
Load variation influence | 0.8% max. (0 to 100% load, rated input voltage) | |||
Temperature variation influence | 0.05%/ °C max. (at rated input and output) | |||
Startup time | 500 ms max. (up to 90% of output voltage at rated input and output) | |||
Hold time *3 | 20 ms min. | |||
Addi-
tional func- tions |
Overload protection *6 | 105% to 175% of rated load current, voltage drop, intermittent, automatic
reset |
||
Overvoltage protection *7 | Yes | |||
Overheat protection | No | |||
Parallel operation | No (However, backup operation is possible; external diodes required.) | |||
Series operation | Yes (For up to two Power Supplies; external diodes required.) | |||
Protective circuit operation
indicator |
No | |||
Other | Ambient operating temperature | Refer to the derating curve in Engineering Data on Catalog (with no icing
or condensation). |
||
Storage temperature | - 25 to 65 °C (with no icing or condensation) | |||
Ambient operating humidity | 25% to 85% (Storage humidity: 25% to 90%) | |||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current:
20 mA) 2.0 kVAC for 1 min. (between all inputs and PE terminals; detection current: 20 mA) 1.0 kVAC for 1 min. (between all outputs and PE terminals; detection current: 20 mA) |
|||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/PE terminals) at 500
VDC |
|||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z
directions |
|||
Shock resistance | 150 m/s2 , 3 times each in ± X, ± Y, ± Z directions | |||
Output indicator | Yes (Color: Green) | |||
EMI | Conducted
Emissions |
Conforms to EN 55011 Group 1 Class A and based on FCC Class A *9 | ||
Radiated Emissions | Conforms to EN 55011 Group 1 Class A *9 | |||
EMS | Electrostatic
Discharge |
Conforms to EN61000-4-2 | ||
Radiated
Electromagnetic Field |
Conforms to EN61000-4-3 | |||
Electrical Fast
Transient/Burst |
Conforms to EN61000-4-4 | |||
Surge | Conforms to EN61000-4-5 | |||
Conducted
Disturbance |
Conforms to EN61000-4-6 | |||
Voltage Dips/Short
Interruptions |
Conforms to EN61000-4-11 | |||
Approved standards *9 | UL Listed: UL 508 (Listing), UL UR: UL 60950-1 (Recognition) | |||
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No. 60950-1 |
||||
EN/VDE: EN50178 (= VDE 0160) Over voltage category III,
EN 60950-1 (= VDE 0805 Teil 1) (Terminal block: Based on DIN 50274 (VDE 0660-514)) |
||||
SEMI | SEMI F47-0200 (200-VAC input) | |||
Weight *8 | 250 g max. |