Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

Lead Contents

FAQ00856 of Programmable Controllers FAQ

FAQ No. FAQ00856

Primary Contents

Question

When using C200H-CT001-V1/CT002/CT021 High-speed Counter Units, the RUN indicator does not light even when I turn ON power supplies to Programmable Controllers. Is the Unit malfunctioning?

Answer



The RUN indicator on High-speed Counter Units lights when count operations begin. The conditions under which count operation will begin depend on the operating mode.

Example:
Using C200H-CT001-V1 in Linear Operating Mode

When bit 00 of word n allocated to the High-speed Counter Unit turns ON, the counting operation will begin, and the RUN indicator will light.

n = 100 +10 x Unit number for the C200HX/HG/HE, C200HS, or C200H
n = 2000 + 10 x Unit number for a CS1-series Programmable Controllers