Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

Lead Contents

FAQ03159 of Timers FAQ

FAQ No. FAQ03159

Primary Contents

Question

What is a substitute product for ATS Pneumatic Timers?

Answer



1.It depends on ATS model. Refer to the following table.

Operating modeON-delayOFF-delay
Operating methodOver-voltage time-limit operationNon-voltage time-limit operation
Reset methodSelf-resetElectric reset
ContactsTime-limitSPST-NO/SPST-NC
Instantaneous---SPST-NOSPST-NO/
SPST-NC
---SPST-NOSPST-NO/
SPST-NC
Power supplyACDCACACDCAC
ModelATSATS-10ATS-11ATSATS-10ATS-11
ON-delay operationOFF-delay operation
(1)
H3CR-A8 + P2CF-8
(2)
H3CR-A8E + P2CF-8
(3)
H3CR-H8L +
P2CF-8
(4)
H3CR-H8L + P2CF-8 +
External Relay

Note:

1.The ON-delay and OFF-delay operation of ATS could be specified by the orientation of the magnet section. Therefore there is no difference between the models with regards to the operating mode. When the moving part of the magnet section was at the bottom, it specified ON-delay operation, and when it was at the top, it specified OFF-delay operation.

2.he bottom row gives recommended substitute products or models with substitute functions. For details, refer to the following information.

2.There is no substitute product in column (1) because ATS utilizes the flow characteristics of air, which significantly differs in principle and construction with the current mainstream digital timers.
However, a substitute function can be created by using H3CR-A8 Solid-state Timer with P2CF-8 Surface Mounting Sockets.

3.There is no substitute product in column (2).
However, a substitute function can be created by using H3CR-A8E with instantaneous contacts with P2CF-8.

4.There is no substitute product in column (3).
However, a substitute function can be created by using H3CR-H8L OFF-delay Timers with P2CF-8.

5.There is no substitute product in column (4).
However, a substitute function can be created by using H3CR-H8L with P2CF-8, and creating an instantaneous contact with an external relay.

6.General Comparison of ATS and H3CR-A/H

Compared itemATSH3CR-A8(E), -H8LRemarks
Operating principleMechanical principle using the flow of airDigital
Mounting methodSurface mounting only
Mounting direction limited
Surface mounting and flush mounting
No linit to mounting direction
External
connections
Top screw terminal8-pin socket
Supply voltage100 VAC, 50 Hz/100/110 VAC, 60 Hz
110 VAC, 50/60 Hz
200 VAC, 50 Hz/200/220 VAC, 60 Hz
220 VAC, 50/60 Hz
440 VAC, 50/60 Hz
24, 48, 100, 110 VDC only
H3CR-A8(E):
100 to 240 VAC/100 to 125 VDC
24 to 48 VAC/12 to 48 VDC
H3CR-H8L:
100/110/120 VAC
200/220/240 VAC
24 VAC/VDC, 48 VDC, 100 to 125 VDC only
See
note 1.
Set time range0.2 s to 200 sH3CR-A8(E): 0.05 s to 300 h
H3CR-H8L:
S Series: 0.05 s to 12 s
M Series: 0.05 min. to 12 min.
See
note 2.
Contact output
electrical
life expectancy
1,000,000 operations min.
(6 A at 250 VAC, resistive load)
100,000 operations min.
(5 A at 250 VAC, resistive load)
See
note 3.

Note:

1.There are no H3CR-A8, -H8 models that operate at 440 VAC. The voltage must be stepped down.

2.If using the M-series H3CR-H8L, secure at least a 2-s power ON time. Do not use the H3CR-H8L Timer with a repeat period of less than 3 s.

3.The electrical durability of the time-limit and instantaneous contacts drop when large loads are used. Install an external replay as required.

Recommended Products

K3HB-X

A Process Indicator Ideal for Discriminating and Displaying Measurements for Voltage/Current Signals

E5CN-H

A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function.

H5CZ

Easy to Use and Easy to Read.

Other Timers FAQ