FAQ03126 of Timers FAQ

FAQ No. FAQ03126

Primary Contents

Question

What is a substitute product for STP Motor Timers?

Answer



1.It depends on STP model. Refer to the following table.

Operating methodTime-limit operation
Reset methodSelf-resetElectric reset
Internal connectionParallel motor and clutch connectionSeparate motor and clutch connection
Time-limit contactSPDTSPDT
Instantaneous contactSPST-NO'SPST-NOSPDTSPST-NO'---
Without moving
pointer
Surface mountingSTP-NSTP-NHSTP-NDSTP-N2STP-NR
Flush mountingSTP-YSTP-YHSTP-YD---STP-YR
Recommended substitute product
or models with substitute functions
(1) H3CR-A8E(3) H2C-F(4) H2C-8R
With moving
pointer
Surface mountingSTP-NMSTP-NMHSTP-NMDSTP-NM2STP-NMR
Flush mountingSTP-YMSTP-YMHSTP-YMD---STP-YMR
Recommended substitute product
or models with substitute functions
(2) H2C-8(3) H2C-F(4) H2C-8R

Note:For details of the recommended substitute products or models with substitute functions, refer to the following information.

2.The substitute product in column (1) is H3CR-A8E Solid-state Timers because digital Timers have higher integrated performance than motor Timers when there are no moving pointers.
It is recommended that the socket is changed to P2CF-08 Sockets for a surface mounting timer. If you continue to use 8PFA Sockets, it must be used with Y92F-42 Adaptors, and PL08 Sockets with Y92H-7 Hold-down Clips.
When using a flush mounting model, Y92F-73 Flush Mounting Adaptors are required because H3CR is smaller than STP.
For Timers with SPST-NO instantaneous contacts, the power supply terminal 2 and instantaneous contact terminal 1 must be externally shorted for H3CR-A8E because they are internally shorted in STP.
Otherwise, no additional wiring or wiring changes are required.

3.The substitute product in column (2) is H2C-8 Motor Timers with moving pointer because only Motor Timers can replicate the moving pointer function.
It is recommended that the sockets are changed to P2CF-08 for surface mounting Timers. If you continue to use 8PFA Sockets, they must be used with Y92F-42 Adaptors, and PL08 Sockets with Y92H-1 Hold-down Clips.
When using a flush mounting model, Y92F-70 Flush Mounting Adaptors are required because H2C is smaller than STP.
For Timers with SPST-NO’ instantaneous contacts, the power supply terminal 2 and instantaneous contact terminal 1 must be externally shorted for H2C-8 because they are internally shorted in STP.
Otherwise, no additional wiring or wiring changes are required.

4.The substitute product in column (3) is H2C-F Motor Timers with top screw terminals because Timers with socket wiring do not have a function for separate motor and clutch connection.
STP socket wiring and H2C-F top wiring are irrelevant and so a large change in wiring is required.
The mounting method also must change from STP sockets to DIN track or screw mounting.

5.The substitute product in column (4) is the electrically reset H2C-8R Motor Timers.
It is recommended that the socket is changed to P2CF-08 for a surface mounting timer. If you continue to use 8PFA Sockets, it must be used with sY92F-42 Adaptors, and sPL08 Sockets with Y92H-1 Hold-down Clips.
When using a flush mounting model, Y92F-70 Flush Mounting Adaptors are required because H2C is smaller than STP.

6.General Comparison of STP and H3CR-A/H2C

Compared
item
STPH3CR-AH2C
Supply
voltage
100 VAC 50/60 Hz/110 VAC 60 Hz
200 VAC 50/60 Hz/220 VAC 60 Hz
100 to 240 VAC, 50/60 Hz/100 to 125 VDC
24 to 48 VAC 50/60 Hz/12 to 48 VDC
100 VAC 50/60 Hz/110 VAC 60 Hz
200 VAC 50/60 Hz/220 VAC 60 Hz
Time
range
13 types: 1 scale 1 range 5 s to 24 h1 type: 4 scales 4 ranges one multitimer3 settings (choose from A, B, C):
1 scale, 5 ranges, 1 multitimer
A: 30 s, 3 min, 30 min, 3 h, 30 h
B: 6 s, 60 s, 6 min, 60 min, 6 h
C: 12 s, 120 s, 12 min, 120 min, 12 h