Question

What is the method for turning the output ON and OFF at specific times for the whole year?

Answer



Use the H5S's cyclic operation function.

1. Press the Cycle/Pulse Key.

2. Select all the days of the week (Sunday to Saturday).

3. Set the cycle to start at AM 0:00.

4. Set the cycle to stop at PM 11:59.

5. Set the ON time length.

6. Set the OFF time length.

For the above settings, the output must be OFF for one minute starting at 11:59.

Starting and stopping from different times is also possible.

However, the ON time length and OFF time length combined must be divisible by 24 hours.