Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

G32A-B

AC Input Unit

G32A-B

AC Input Unit Enabling AC Operation

Ratings (at an Ambient Temperature of 25°C)

Item Rated input voltage
100/120 VAC 200/240 VAC
Rated input current 50 Hz 100 (200) VAC 21.4 mA TYP 20.9 mA TYP
120 (240) VAC 26.5 mA TYP 25.4 mA TYP
60 Hz 100 (200) VAC 25.4 mA TYP 24.9 mA TYP
120 (240) VAC 31.6 mA TYP 30.3 mA TYP
Must operate voltage 75% max. of the rated voltage 75% max. of the rated voltage
Must release voltage 10% min. of the rated voltage 10% min. of the rated voltage
Output voltage/current 12 VDC ±15%/15 mA max. 12 VDC ±15%/15 mA max.

Characteristics

Item Rated input voltage
100/120 VAC 200/240 VAC
Input voltage range 75 to 132 VAC 150 to 264 VAC
Operate time 1.5 cycles max. of load power supply
Release time 1.5 cycles max. of load power supply
Vibration resistance 10 to 55 to 10 Hz, 0.375-mm single amplitude (when mounted to DIN track)
Shock resistance 300 m/s2 (Approx. 30 G)
Ambient temperature Storage: -30 to 100°C (with no icing or condensation)
Operating: -30 to 80°C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Weight Approx. 80 g