Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

DRT2-[]D16S(-1)

e-CON Connector Terminals

DRT2-[]D16S(-1)

Includes Sensor Connector That Conforms to Industry Standards And Can Be Used to Connect Sensors with Pre-wired Cables without Using Special Tools.

about this Product Family

General Specifications

Model DRT2-ID16S(-1) DRT2-MD16S(-1)
Communications power supply
voltage
11 to 25 VDC
Unit power supply voltage Not required (Supplied from the communications connector.)
I/O power supply voltage 20.4 to 26.4 VDC (24 VDC -15%/+10%)
Current consumption Communications power supply: 230 mA max. Communications power supply: 135 mA max.
Dielectric strength 500 VAC between isolated circuits
Noise immunity Conforms to IEC61000-4-4, 2 kV (power line)
Vibration resistance 10 to 60 Hz, 0.7-mm double amplitude, 60 to 150 Hz, 50 m/s2 for 80 min each in the X, Y, and
Z directions
Shock resistance 150m/s2, 6 directions, 3 times each
Mounting method DIN 35 mm-track mounting or M4 screw mounting
Screw tightening torque M2 (communications connector screws): 0.26 to 0.3 Nm
M4 (unit mounting): 0.6 to 0.98 Nm
Ambient operating temperature -10°C to 55°C
Ambient operating humidity 25 to 85% (with no condensation)
Ambient storage temperature -25°C to 65°C
Weight 90 g max. 95 g max.

Output Specifications

Terminals with 8 Inputs and 8 Outputs

Model DRT2-MD16S DRT2-MD16S-1
Internal I/O common NPN PNP
I/O points 8 outputs (8 to 15)
Rated output current 0.3 A/point, 2.4 A/common 0.3 A/point, 1.6 A/common
Residual voltage 1.2 VDC max.
(0.3 A DC between output and G terminal)
1.2 VDC max.
(0.3 A DC between output and V terminal)
Leakage current 0.1 mA max.
ON delay time 1.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits per common 8 per common
Load short-circuit detection current 2.4 A min./common 1.6 A min./common

Input Specifications

Terminals with 16 Inputs

Model DRT2-ID16S DRT2-ID16S-1
Internal I/O common NPN PNP
I/O points 16 inputs
ON voltage 9 VDC min. (between each input terminal and V) 9 VDC min. (between each input terminal and G)
OFF voltage 5 VDC max. (between each input terminal and V) 5 VDC max. (between each input terminal and G)
OFF current 1 mA max.
Input current 11 mA max./point (at 24 VDC)
3.0 mA min./point (at 11 VDC)
ON delay time 1.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits per common 16 per common
Sensor short-circuit detection
current
The total current for all of the following input points is monitored to detect sensor short-circuits.
IN0/IN1, IN2/IN3, IN4/IN5, IN6/IN7, IN8/IN9, IN10/IN11, IN12/IN13, IN14/IN15

Terminal with 8 Inputs/8 Outputs

Model DRT2-MD16S DRT2-MD16S-1
Internal I/O common NPN PNP
I/O points 8 inputs (0 to 7)
ON voltage 9 VDC min. (between each input terminal and V) 9 VDC min. (between each input terminal and G)
OFF voltage 5 VDC max. (between each input terminal and V) 5 VDC max. (between each input terminal and G)
OFF current 1 mA max.
Input current 11 mA max./point (at 24 VDC)
3.0 mA min./point (at 11 VDC)
ON delay time 1.5 ms max.
OFF delay time 1.5 ms max.
Number of circuits per common 8 per common
Sensor short-circuit detection
current
The total current for all of the following input points is monitored to detect sensor short-circuits.
IN0/IN1, IN2/IN3, IN4/IN5, IN6/IN7