Model | GLS-1 | GLS-1L | |
---|---|---|---|
Sensing distance | 15 mm *1 | ||
Contact circuit | SPST-NO | ||
Switching capacity *2 | Maximum operating voltage: 100 VDC
Maximum operating current: 0.1 A DC Maximum switching capacity: 10 W (for both open and closed contacts) |
||
Contact dielectric strength | 250 VDC for 1 min with a leakage current of 1 mA max. | ||
Response frequency | 20 Hz max. | ||
Ambient temperature range | Operating/Storage: -20 to 60°C (with no icing or condensation) | ||
Ambient humidity range | Operating/storage: 35% to 85% (with no condensation) | ||
Contact resistance | 150 mΩ max. | 250 mW max. (including conductor resistance of lead wire) | |
Dielectric strength | 1,000 VAC for 1 min between terminals and case | ||
Life expectancy | 50,000,000 times min. with 0.1-A resistive load at 24 VDC | ||
Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | ||
Shock resistance | Destruction: 300 m/s2 3 times each in X, Y, and Z directions | ||
Degree of protection | IP40 (IEC) | ||
Connection method | Terminal block | Pre-wired (standard cable length: 1 m) | |
Materials | Sensor | ABS | |
Magnet |
*2. AC power cannot be used.