Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

TL-L

Ultra-long Sensing-distance Proximity Sensor

TL-L

Detection Distance of 100 mm for Both Ferrous and Non-ferrous Substances.

Output specifications Current output
TL-L100-7
Sensing distance 100 mm ±10%
Set distance 0 to 80 mm
Differential travel 15% max. of sensing distance
Detectable object Ferrous metal and non-ferrous metal
Standard sensing object Iron, 200 × 200 × 1 mm
Response time 100 ms max.
Power supply voltage
(operating voltage range)
10 to 30 VDC including 10% ripple (p-p)
Current consumption 40 mA DC max.
Control output 200 mA DC max. (residual voltage: 1 V max.)
Indicators Operation indicator (red)
Operation mode
(with sensing object approaching)
NO; For details, refer to Datasheet
Protection circuits Reverse polarity protection, Surge suppressor
Ambient temperature range Operating/Storage: -25 to 55°C (with no icing or condensation)
Ambient humidity range Operating/Storage: 35% to 95% (with no condensation)
Temperature influence ±30% max. of sensing distance at 20°C in the temperature range of -10 to 40°C
Voltage influence ±5% max. of sensing distance at rated voltage in rated voltage ±10% range
Insulation resistance 5 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 500 VAC, 50/60 Hz for 1 min between current-carrying parts and case
Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance Destruction: 200 m/s2 10 times each in X, Y, and Z directions
Degree of protection IP66 (IEC)
Connection method Pre-wired Models (Standard cable length: 1m)
Weight (packed state) Approx. 1.5 kg
Materials Case: Aluminum die-cast, Sensing surface: Epoxy resin
Accessories Instruction manual