Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

E2EC

Cable Amplifier Proximity Sensor

E2EC

Subminiature Sensors with Long-distance Detection

Model DC 2-Wire Models DC 3-Wire Models
E2EC-CR8D[] E2EC-C1R5D[] E2EC-C3D[] E2EC-X4D[] E2EC-CR5C1 E2EC-C2R5C1
Sensing distance 0.8 mm ±15% 1.5 mm ±10% 3 mm ±10% 4 mm ±10% 0.5 mm ±15% 2.5 mm ±10%
Set distance 0 to 0.56 mm 0 to 1.05 mm 0 to 2.1 mm 0 to 2.8 mm 0 to 0.3 mm 0 to 1.7 mm
Differential travel 10% max. of sensing distance
Detectable object Ferrous metal (The sensing distance decreases with non-ferrous metal. Refer to Data Sheet.)
Standard sensing
object
Iron, 5 × 5 × 1 mm Iron, 8 × 8
× 1 mm
Iron, 12 × 12
× 1 mm
Iron, 5 × 5
× 1 mm
Iron, 8 × 8 ×
1 mm
Response frequency
*1
1.5 kHz 1 kHz
Power supply voltage
(operating voltage
range)
12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max. 5 to 24 VDC (4.75 to 30 VDC),
ripple (p-p): 10% max.
Current
consumption
--- 10 mA max.
Leakage current 0.8 mA max. ---
Control
output
Load
current
5 to 100 mA NPN open-collector output,
100 mA max. (30 VDC max.)
Residual
voltage
3 V max. (Load current: 100 mA, Cable length: 2 m) 1 V max. (Load current:
100 mA, Cable length: 2 m)
Indicators D1 Models: Operation indicator (red), Setting indicator (green)
D2 Models: Operation indicator (red)
Detection indicator (red)
Operation mode
(with sensing object
approaching)
D1 Models: NO
D2 Models: NC
Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details.
NO
Refer to the timing charts
under I/O Circuit Diagrams on
Data Sheet for details.
Protection circuits Load short-circuit protection, Surge suppressor Surge suppressor
Ambient
temperature range
Operating/Storage: -25 to 70°C (with no icing or condensation) *2
Ambient
humidity range
Operating/Storage: 35% to 95% (with no condensation)
Temperature
influence
±20% max. of sensing distance at 23°C in the temperature range of -25 to 70°C
Voltage influence ±2.5% max. of sensing distance at rated voltage in the rated voltage ±15% range ±5% max. of sensing distance
at the rated voltage range
in the voltage range of 4.75 to
30 V
Insulation
resistance
50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 1,000 VAC for 1 min between current-carrying parts and case 500 VAC for 1 min between
current-carrying parts and
case
Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions Destruction: 500 m/s2 10 times
each in X, Y, and Z directions
Degree of protection IEC 60529 IP67, In-house standards: oil-resistant (For Sensor Head only) IEC 60529 IP64
Connection method Pre-wired Models (Standard cable length: 2 m)
Weight
(packed state)
Approx. 45 g
Materials Case Brass
Sensing
surface
ABS
Clamping
nut
--- Brass
(nickel-plated)
---
Toothed
washer
--- Iron (zinc-plated) ---
Accessories Amplifier Mounting Bracket, Instruction manual Instruction manual

*1. The response frequency is an average value.
       Measurement conditions are as follows: standard sensing object, a distance of twice the standard sensing object,
       and a set distance of half the sensing distance.
*2. Incorrect operation may occur if there is a large temperature difference between the Sensor Head and the Amplifier
       Unit.