Model | KM-N3-FLK | |
---|---|---|
Applicable phase wiring methods | Single-phase two-wire, single-phase three-wire, three-phase three-wire,
and three-phase four-wire |
|
Number of measured circuits | Single-phase two-wire: 4 circuits max., Single-phase three-wire or three-
phase three-wire: 2 circuits max., Three-phase four-wire: 1 circuit |
|
Power supply voltage
(operating frequency) |
100 to 240 VAC (50/60 Hz) | |
Power supply allowable voltage range | 85% to 110% of rated power supply voltage | |
Power consumption | 7 VA max. | |
Input | Rated input voltages | Single-phase, 2-wire:100 to 277 VAC
Single-phase, 3-wire:100 to 240 VAC (L-N) or 200 to 480 VAC (L-L) Three-phase, 3-wire: 173 to 480 VAC (L-L) Three-phase, 4-wire: 100 to 277 VAC (L-N) or 173 to 480 VAC (L-L) |
Allowable supply voltage range | 85% to 115% of rated power supply voltage | |
Connectable CTs | General-purpose CT with a rated secondary current of 1A or 5A * | |
Maximum CT secondary current | 6A | |
Rated input frequency | 50/60 Hz | |
Ambient operating temperature | -25 to 55°C (with no condensation or icing) | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 85°C (with no condensation or icing) | |
Storage humidity | 25% to 85% | |
Operating altitude | 2,000 m max. | |
Installation environment | Overvoltage category II, measurement category II, pollution degree 2 | |
Electromagnetic environment | Industrial electromagnetic environment (EN/IEC 61326-1 Table 2) | |
Compliant standards | EN 61010-2-030, EN 61326-1, and UL 61010-1 |