Rated input voltage | K8DT-PZ1[]N: Three-phase, three-wire Mode: 200, 220, 230, or 240 VAC
K8DT-PZ2[]N: Three-phase, three-wire Mode: 380, 400, 415, or 480 VAC |
|
---|---|---|
Input load | K8DT-PZ1: Approx. 1.7 VA
K8DT-PZ2: Approx. 2.7 VA |
|
Rated insulation voltage | 528 VAC | |
Operating value setting
range |
Overvoltage/Undervoltage
2% to 30% of rated input voltage Asymmetry 5% to 22% of rated input voltage Note: The rated input voltage can be switched by using the DIP switches. |
|
Operating value | Overvoltage/Undervoltage
Operates at 100% of set value. Asymmetry Asymmetry operating value = Rated input voltage × Asymmetry set value (%) The asymmetry operation will function when the potential difference between the highest and lowest voltage phases equals or exceeds the asymmetry operating value. |
|
Reset value | 2% of operating value (fixed) | |
Reset method | Automatic reset | |
Operating
time setting range |
Overvoltage/
Undervoltage |
0.1 to 30 s |
Asymmetry | 0.1 to 30 s | |
Phase
sequence |
0.1 s±0.05 s | |
Phase loss | 0.1 s max. | |
Power ON lock time
(LOCK) |
1 s/5 s (switched by using the DIP switch) | |
Indicators | Power (PWR): Green, Output (OUT): Yellow,
Alarm outputs (ALM): Red |
|
Output form | Relay Output: SPDT contact
Transistor Output: 1 |
|
Output relay ratings | Rated load
5 A at 250 VAC (Resistive load) 5 A at 30 VDC (Resistive load) 1 A at 250 VAC (Inductive load) 0.2 A at 48 VDC (Inductive load) Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations |
|
Transistor output
ratings |
Rated voltage: 24 VDC (maximum voltage: 26.4 VDC)
Maximum current: 50 mA DC |
|
Ambient operating
temperature |
-20 to 60°C (with no condensation or icing) | |
Storage temperature | -25 to 65°C (with no condensation or icing) | |
Ambient operating
humidity |
25% to 85% RH (with no condensation) | |
Storage humidity | 25% to 85% RH (with no condensation) | |
Altitude | 2,000 m max. | |
Applicable wires | Stranded wires, solid wires, or ferrules | |
Applicable wire size | 0.25 to 1.5 mm2 (AWG24 to AWG16) | |
Wire insertion force | 8 N max. for AWG20 wire | |
Screwdriver insertion
force |
15 N max. | |
Wire stripping length | 8 mm | |
Ferrule length | 8 mm | |
Recommended flatblade
screwdriver |
XW4Z-00B (Omron)
SZF 0.4 × 2.5 (Phoenix Contact) 210-719 (Wago) SDI 0.4 × 2.5 × 75 (Weidmuller) |
|
Current capacity | 10 A (per pole) | |
Number of insertions | 50 times | |
Case color | N1.5 | |
Case material | PC, UL 94 V-0 | |
Weight | Approx. 100 g | |
Mounting | Mounts to DIN Track, or screw mounting | |
Dimensions | 17.5 × 90 × 90 mm (W×D×H) |