Rated input voltage | 3-phase, 200 to 480 VAC (3-wire) | |
---|---|---|
Input load | Approx. 4.1 VA | |
Operating time | Phase sequence | 0.1 s±0.05 s |
Phase loss | 0.1 s max. (when the voltage changes rapidly from 100% to 0% of rated voltage) | |
Reset method | Automatic reset | |
Indicators | Power (PWR): Green, Relay output (RY): Yellow | |
Output relays | One DPDT relay (NC operation) | |
Output relay ratings | Rated load
Resistive load 5 A at 250 VAC 5 A at 30 VDC Minimum load: 24 VDC, 4 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC/30 VDC:100,000 operations |
|
Ambient operating temperature | -20 to 60°C (with no condensation or icing) | |
Storage temperature | -25 to 65°C (with no condensation or icing) | |
Ambient operating humidity | 25% to 85% (with no condensation) | |
Storage humidity | 25% to 85% (with no condensation) | |
Altitude | 2,000 m max. | |
Terminal screw tightening torque | 0.49 to 0.59 N·m | |
Terminal wiring method | Recommended wire
Solid wire: 2.5 mm2 Twisted wires: AWG16, AWG18 Note: 1. Ferrules with insulating sleeves must be used with twisted wires. Note: 2. Two wires can be twisted together. Recommended ferrules Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact Al 1-8RD (for AWG18) manufactured by Phoenix Contact Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact |
|
Case color | N1.5 | |
Case material | PC and ABS, UL 94 V-0 | |
Weight | Approx. 130 g | |
Mounting | Mounts to DIN Track. | |
Dimensions | 22.5 × 90 × 100 mm (W×H×D) |