Power supply
voltage |
Isolated power supply | 24 VAC/DC
100 to 240 VAC |
---|---|---|
Power consumption | 24 VAC/DC: 1.8 VA/1.0 W max.
100 to 240 VAC: 3.5 VA max. |
|
Rated input voltage | 3-phase, 200 to 480 VAC (3-wire) | |
Operating
time |
Phase sequence on three-
phase voltage input |
0.1 s±0.05 s |
Phase loss on three-phase
voltage input |
0.1 s max. (when the voltage changes rapidly from 100% to 0% of rated
voltage) |
|
PTC thermistor input | 0.2 s max. | |
Reset method | Manual reset/automatic reset (switchable)
Note: Manual reset method: Press the TEST/RESET button. |
|
Indicators | Power (PWR): Green, PH_Alarm outputs (ALM): Red, TS_Alarm outputs
(ALM): Red |
|
Output relays | One SPDT relay output (normally closed operation) | |
Output relay ratings | Rated load
Resistive load 5 A at 250 VAC 5 A at 30 VDC Maximum switching capacity: 1,250 VA, 150 W Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations |
|
Ambient operating temperature | -20 to 60°C (with no condensation or icing) | |
Storage temperature | -25 to 65°C (with no condensation or icing) | |
Ambient operating humidity | 25% to 85% (with no condensation) | |
Storage humidity | 25% to 85% (with no condensation) | |
Altitude | 2,000 m max. | |
Terminal screw tightening torque | 0.49 to 0.59 Nm | |
Terminal wiring method | Recommended wire
Solid wire: 2.5 mm2 Twisted wires: AWG16, AWG18 Note: 1. Ferrules with insulating sleeves must be used with twisted wires. 2. Two wires can be twisted together. Recommended ferrules Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact Al 1-8RD (for AWG18) manufactured by Phoenix Contact Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact |
|
Case color | N1.5 | |
Case material | PC and ABS, UL 94 V-0 | |
Weight | Approx. 150 g | |
Mounting | Mounts to DIN Track. | |
Dimensions | 22.5 × 90 × 100 mm (W × H × D) |