Function name |
Specifications |
Enclosure ratings *1 |
Open type (IP20) |
Control |
Control method |
Phase-to-phase sinusoidal modulation PWM |
Output frequency range
*2 |
0.10 to 400 Hz (or 580 Hz in the high-frequency mode; restrictions apply) |
Frequency precision *3 |
Digital command: ±0.01% of the max. frequency, Analog command: ±0.2% of
the max. frequency (25±10 °C) |
Frequency setting
resolution |
Digital setting: 0.01 Hz, Analog setting: One-thousandth of the maximum
frequency |
Voltage/Frequency
characteristics |
V/f characteristics (constant/reduced torque)
Sensorless vector control, V/f control with speed feedback |
Overload current rating |
Heavy load rating (CT): 150%/60 s
Light load rating (VT): 120%/60 s |
Instantaneous
overcurrent protection |
200% of the value of heavy load rating (CT) |
Acceleration/
Deceleration time |
0.01 to 3600 s (linear/curve selection), acceleration/deceleration 2 setting
vailable |
Carrier frequency
adjustment range |
2 to 15 kHz (with derating) |
Starting torque |
200%/0.5 Hz (sensorless vector control) |
External DC injection
braking |
Starts at a frequency lower than that in deceleration via the STOP command,
at a value set lower than that during operation, or via an external input. (Level
and time settable). |
Protective functions |
Overcurrent, overvoltage, undervoltage, electronic thermal, temperature
error, ground fault overcurrent at power-on status, rush current prevention
circuit, overload limit, incoming overvoltage, external trip, memory error, CPU
error, USP error, communication error, overvoltage suppression during
deceleration, protection upon momentary power outage, emergency cutoff, etc. |
Input
signal |
Frequency settings |
Digital Operator
External analog input signal: 0 to 10 VDC/4 to 20 mA, Modbus communication
(Modbus-RTU) |
RUN/STOP command |
Digital Operator
External digital input signal (3-wire input supported), Modbus communication
(Modbus-RTU) |
Multi-function input |
7 points (Selectable from 59 functions) |
Analog input |
2 points (Voltage FV terminal: 10 bits/0 to 10 V, Current FI terminal: 10 bits/4
to 20 mA) |
Pulse input |
1 point (RP terminal: 32 kHz max., 5 to 24 VDC) |
Output
signal |
Multi-function output |
2 points (P1/EDM, P2; selectable from 43 functions) |
Relay output |
1 point (1c contact: MC, MA, MB; selectable from 43 functions) |
Analog output
(Frequency monitor) |
1 point (AM terminal: Voltage 10 bits/0 to 10 V) (Frequency, current selectable) |
Pulse output |
1 point (MP terminal: 32 kHz max., 0 to 10 V) |
Communi-
cations |
RS-422 |
RJ45 connector (for Digital Operator) |
RS-485 |
Control circuit terminal block, Modbus communication (Modbus-RTU) |
USB |
USB1.1, mini-B connector |
Drive Programming *4 |
Calculate, Logic, Control I/O and so on |
Other functions |
AVR function, V/f characteristics switching, upper/lower limit, 16-step
speeds, starting frequency adjustment, jogging operation, carrier frequency
adjustment, PID control, frequency jump, analog gain/bias adjustment, S shape
acceleration/deceleration, electronic thermal characteristics, level
adjustment, restart function, torque boost function, fault monitor, soft lock
function, frequency conversion display, USP function, motor 2 control function,
UP/DWN, overcurrent control function, etc. |
Operating
environ-
ment |
Ambient operating
temperature |
-10 to 50 °C (However, derating is required). |
Ambient storage
temperature |
-20 °C to 65 °C |
Ambient operating
humidity |
20% to 90% RH (with no condensation) |
Vibration resistance |
5.9 m/s2 (0.6G), 10 to 55 Hz |
Application
environment |
At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust) |
Options |
EtherCAT
Communication Unit |
3G3AX-MX2-ECT |
CompoNet
Communication Unit |
3G3AX-MX2-CRT-E |
DeviceNet
Communication Unit |
3G3AX-MX2-DRT-E |
Other option |
DC reactor, AC reactor, radio noise filter, input noise filter, output noise filter,
regenerative braking unit, Braking Resistor, etc. |
Interna-
tional
standard |
EC di-
rective |
EMC directive |
EN61800-3: 2004 |
Low voltage
directive |
EN61800-5-1: 2007 |
Machinery
directives |
IEC 60204-1 Stop Category 0, EN IEC 61800-5-2 (STO), EN ISO 13849-1: 2008
(PLd) |
UL/cUL |
UL508C |