Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

61F-G[]

Floatless Level Switch (Basic Type)

61F-G[]

Basic Building-block Controllers That Mount Directly to Panels for Easier Maintenance

about this Product Family

Standard Models

Items General-purpose
Controller
61F-[] (TDL)
*1, *2
High-temperature
Controller
61F-[]T
*1
Long-distance Controllers
61F-[]L 2KM (for 2 km)
61F-[]L 4KM (for 4 km)
*1
Controlling materials
and operating
conditions
For control of
ordinary purified
water or sewage
water
For control of ordinary
purified water or sewage
water in cases where the
ambient temperature is
high.
For control of ordinary purified water in
cases where the distance between sewage
pumps and water tanks or between
receiver tanks and supply tanks is long or
where remote control is required.
Supply voltage 100, 110, 120, 200, 220 or 240 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
InterElectrode voltage 8 VAC
InterElectrode current Approx. 1 mA AC max.
Power consumption 61F-G[]: 3.5 VA max.; G1F-G1[], G1F-G2[], or G1F-I[]: 5.5 VA max.; G1F-G3[]: 7.5 VA max.;
G1F-G4[]: 14.5 VA max.
InterElectrode operate
resistance
0 to approx. 4 kΩ 0 to approx. 5 kΩ 0 to approx. 1.8 kΩ (for 2 km)
0 to approx. 0.7 kΩ (for 4 km)
InterElectrode release
resistance
Approx. 15 k to ∞ Ω Approx. 15 k to ∞ Ω 4 k to ∞ Ω (for 2 km)
2.5 k to ∞ Ω (for 4 km)
Cable length *3 1 km max. 600 m max. 2 km max.
4 km max.
Control output 2 A, 220 VAC (Inductive load: cosφΦ = 0.4)
5 A, 220 VAC (Resistive load)
Ambient temperature Operating: -10 to 55°C (-10 to 70°C for 61F-[]T)
Ambient humidity Operating: 45% to 85% RH
Insulation resistance *4 100 MΩ min. (at 500 VDC)
Dielectric strength *4 2000 VAC, 50/60 Hz for 1 min.
Life expectancy Electrical: 500,000 operations min.
Mechanical: 5,000,000 operations min.
Weight 61F-G[]: Approx. 380 g, G1F-G1[], G1F-G2[], or G1F-I[]: Approx. 750 g; G1F-G3[]: Approx.
930 g; G1F-G4[]: Approx. 1,710 g

Items High-sensitivity
Controllers
61F-[]H *1
Low-sensitivity
Controller
61F-[]D *1
Two-wire Controller
61F-[]R *1
Controlling materials
and operating
conditions
For control of liquids
with high specific
resistance such as
distilled water
For control of liquids with
low specific resistance
such as salt water, sewage
water, acid chemicals,
alkali chemicals
For control of ordinary purified water
or sewage water used in combination
with Two-wire Electrode Holder
(incorporating a resistor of 6.8 kΩ)
It is possible to wire with less than one
wiring against general 61F's wiring.
Supply voltage 100, 110, 120, 200, 220 or 240 VAC; 50/60 Hz
Operating voltage range 85% to 110% of rated voltage
InterElectrode voltage 24 VAC 8 VAC
InterElectrode current Approx. 1 mA AC max.
Power consumption 61F-G[]: 3.5 VA max.; G1F-G1[], G1F-G2[], or G1F-I[]: 5.5 VA max.; G1F-G3[]: 7.5 VA max.;
G1F-G4[]: 14.5 VA max.
InterElectrode operate
resistance
Approx. 15 kΩ to
70 kΩ *5
0 to approx. 1.8 kΩ 0 to approx. 1.1 kΩ
InterElectrode release
resistance
Approx. 300 k to ∞ Ω Approx. 5 k to ∞ Ω Approx. 15 k to ∞ Ω
Cable length *3 50 m max. 1 km max. 800 m max.
Control output 2 A, 220 VAC (Inductive load: cosφΦ = 0.4)
5 A, 220 VAC (Resistive load)
Ambient temperature Operating: -10 to 55°C (-10 to 70°C for 61F-[]T)
Ambient humidity Operating: 45% to 85% RH
Insulation resistance *4 100 MΩ min. (at 500 VDC)
Dielectric strength *4 2000 VAC, 50/60 Hz for 1 min.
Life expectancy Electrical: 500,000 operations min.
Mechanical: 5,000,000 operations min.
Weight 61F-G[]: Approx. 380 g, G1F-G1[], G1F-G2[], or G1F-I[]: Approx. 750 g; G1F-G3[]: Approx.
930 g; G1F-G4[]: Approx. 1,710 g

*1. The [] in the model name represents G, G1, G2, G3, G4, and I.
*2. The suffix "TDL" attached to the model name represents models designed for tropical regions (storage humidity of
       45% to 90%). For details, refer to Safety Precautions for Floatless Level Controllers.
*3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will
       become shorter as the cable diameter or number of conductors becomes larger. For details, refer to Safety
       Precautions for Floatless Level Controllers.
*4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals,
       between power terminals and contact terminals, and between Electrode terminals and contact terminals.
*5. Possible to use with 15 kΩ or less, however, this may cause reset failure.
*6. High-sensitivity Controllers use advanced operation.
       When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation
       electrodes), the internal relay will not operate.
       When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation
       electrodes), the internal relay will operate.

Advanced Operation

With advanced operation, the internal relay operates as soon as control power is supplied to the G1F and is reset when current flows between the poles. Wiring is the same as for models with sequential operation.