Rated supply voltage | 24 VDC | |
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 1.5 W max. (for max. DC load) (Inrush current: 15 A max.) | |
Mounting method | Flush mounting | |
External connections | Screw terminals (M3 screws) | |
Terminal screw tightening
torque |
0.5 Nm max. | |
Attachment | Waterproof packing, flush mounting bracket | |
Display | 7-segment, negative transmissive LCD; time display (h, min, s); CMW, OUT, RST, TOTAL
Present value (red, 7-mm-high characters); Set value (green, 3.4-mm-high characters) |
|
Digits | PV: 4 digits
SV: 4 digits When total count value is displayed: 8 digits (Zeros suppressed) |
|
Memory backup | EEPROM (non-volatile memory) (number of writes: 100,000 times) | |
Counter | Maximum
counting speed |
30 Hz or 5 kHz * |
Counting range | -999 to 9,999 | |
Input modes | Increment, decrement, individual, quadrature inputs | |
Output modes | N, F, C, or K | |
Timer | Time ranges | 0.000 to 9.999 s, 0.00 to 99.99 s, 0.0 to 999.9 s, 0 to 9999 s, 0 min 00 s to 99 min
59 s, 0.0 to 999.9 min, 0 h 00 min to 99 h 59 min, 0.0 h to 999.9 h, 0 h to 9999 h |
Timer modes | Elapsed time (Up), remaining time (Down) | |
Output modes | A, B, D, E, F, or Z | |
Inputs | Input signals | For Counter: CP1, CP2, and reset
For Timer: Start, gate, and reset |
Input method | No-voltage input (contact short-circuit and open input)
Short-circuit (ON) impedance: 1 kΩ max. (Approx. 2 mA runoff current at 0 Ω) Short-circuit (ON) residual voltage: 2 VDC max. Open (OFF) impedance: 100 kΩ min. Applied voltage: 30 VDC max. |
|
Start, reset, gate | Minimum input signal width: 1 or 20 ms (selectable) | |
Power reset | Minimum power-opening time: 0.5 s | |
Control output | SPDT contact output: 3 A at 250 VAC/30 VDC, resistive load (cosφ = 1) | |
Minimum applied load | 10 mA at 5 VDC (failure level: P, reference value) | |
Reset system | External, manual, and power supply resets (for timer in A, B, D, E, or Z modes) | |
Sensor waiting time | 260 ms max. (Inputs cannot be received during sensor wait time if control outputs are
turned OFF.) |