Rated time | Time setting range | Time division |
---|---|---|
24 hrs x 7 days | 00:00 to 23:59 | 1 min |
Daily Time Switch
about this Product Family
last update: September 24, 2012
Rated time | Time setting range | Time division |
---|---|---|
24 hrs x 7 days | 00:00 to 23:59 | 1 min |
Rated supply voltage | 100 to 240 VAC (50/60 Hz) |
---|---|
Operating voltage range | 85% to 110% of rated supply voltage |
Power consumption | Approx. 4 VA at 240 VAC |
Control outputs | 15 A at 250 VAC, resistive load at 50°C 12 A at 250 VAC, resistive load at 55°C Minimum applied load: 100 mA at 5 VDC (failure level: P, reference value) |
Accuracy of operating time | ±0.01% ±0.05 s max. * |
---|---|
Setting error | |
Influence of voltage | |
Influence of temperature | |
Time accuracy | ±15 s per month (at 25°C) |
Insulation resistance | 100 MΩ min. |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-
current-carrying metal parts and between control power supply circuit and contact control output circuits) 1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
Vibration resistance | Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude |
Shock resistance | Destruction: 300 m/s2 (approx. 30G)
Malfunction: 100 m/s2 (approx. 10G) |
Ambient temperature | Operating: -10°C to 55°C |
Ambient humidity | Operating: 35% to 85% |
Life expectancy | 100,000 operations min. (15 A at 250 VAC, resistive load) |
Approved standards | UL (File No. E52800), CSA (File No. LR22310) |
Weight | Approx. 350 g |
last update: September 24, 2012