A desired time can be set within a range of 0.1 s to 9,990 hrs by combining the three thumbwheel switch modules for time setting and one module for time unit selection.
Solid-state Timer
about this Product Family
last update: September 16, 2015
A desired time can be set within a range of 0.1 s to 9,990 hrs by combining the three thumbwheel switch modules for time setting and one module for time unit selection.
Time unit | 0.1 s | 1 s | 0.1 min | 1 min | 0.1 hrs | 1 hr | 10 hrs | |
---|---|---|---|---|---|---|---|---|
Time range | 1 to 999 (3 digits) |
Item | H3CA-A/H3CA-FA | H3CA-8 | H3CA-8H |
---|---|---|---|
Rated supply voltage
*2 |
24 to 240 VAC (50/60 Hz),
12 to 240 VDC (permissible ripple: 20% max.) |
100/110/120, 200/220/240 VAC, (50/60 Hz), 24 VDC,
110 VDC (permissible ripple: 20% max.) *1 |
|
Operating voltage range | 90% to 110% of rated supply
voltage |
85% to 110% of rated supply voltage | |
Power consumption | AC: approx. 4 VA
DC: approx. 2 W |
AC: approx. 10 VA/1 W
DC: approx. 1 W |
AC: approx. 10 VA/1.5 W
DC: approx. 2 W |
Control outputs | 3 A at 250 VAC, resistive load (cosφ = 1)
Minimum applicable load H3CA-8, H3CA-A and H3CA-FA: 10 mA at 5 VDC (failure level: Preference value) H3CA-8H: 100mA at 5 VDC (failure level: Preference value) Contact materials: Ag-alloy |
*1. Single-phase, full-wave rectified power sources may be used for 24 to 240 VDC.
*2. Refer to Safety Precautions for All Times when combining the Timer with an AC 2-wire proximity sensor.
Accuracy of operating time | ±0.3% ±0.05 s |
---|---|
Influence of voltage | |
Influence of temperature | |
Setting error | ±0.5% ±0.05 s max. |
Reset time | H3CA-A/-FA: 0.5 s max.
H3CA-8H/-8: 0.1 s max. |
Insulation resistance | 100 MΩ min. (at 500 VDC) |
Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts
and between contact and control circuit) 1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts) |
Impulse withstand voltage | 3 kV |
Vibration resistance | Destruction: 10 to 55 Hz with 0.75-mm double amplitude for 1 h each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude for 10 min each in three directions |
Shock resistance | Destruction: 980 m/s2
Malfunction: 98 m/s2 |
Ambient temperature | Operating: -10°C to 55°C |
Ambient humidity | Operating: 35% to 85% |
Life expectancy | Mechanical: 10,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (3 A at 250 VAC, cosφ = 1 at 1,800 operations/h) See Lift-test Curve for more details. |
Approved standards | UL508, CSA C22.2 No. 14, LR, NK
Conforms to EN61812-1. |
EMC | (EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A Emission AC mains: EN55011 Group 1 class A (EMS) EN61812-1 Immunity ESD: IEC61000-4-2 Immunity RF-interference: IEC61000-4-3 Immunity Burst: IEC61000-4-4 Immunity Surge: IEC61000-4-5 Immunity Conducted Disturbance: IEC61000-4-6 Immunity Voltage Dip/Interruption: IEC61000-4-11 |
Weight | H3CA-A: approx. 110 g
H3CA-FA: approx. 190 g |
last update: September 16, 2015