UL508, CSA22.2 No.14, and EN60947-4-3
Solid State Contactors for Heaters
about this Product Family
last update: September 24, 2012
UL508, CSA22.2 No.14, and EN60947-4-3
Model | Same for all models |
---|---|
Rated operating voltage | 12 to 24 VDC |
Operating voltage range | 9.6 to 30 VDC |
Rated input current (impedance) | 10 mA max. (24 VDC) |
Must-operate voltage | 9.6 VDC max. |
Must-release voltage | 1 VDC min. |
Insulation method | Phototriac |
Operation indicator | Yellow LED |
Model | G3PE-
215B- 3(N) |
G3PE-
215B- 2(N) |
G3PE-
225B- 3(N) |
G3PE-
225B- 2(N) |
G3PE-
235B- 3(N) |
G3PE-
235B- 2(N) |
G3PE-
245B- 3(N) |
G3PE-
245B- 2(N) |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 100 to 240 VAC | |||||||
Operating voltage range | 75 to 264 VAC | |||||||
Rated load current *1 | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.2 A | 0.5 A | ||||||
Inrush current resistance
(peak value) |
150 A
(60 Hz, 1 cycle) |
220 A
(60 Hz, 1 cycle) |
440 A
(60 Hz, 1 cycle) |
|||||
Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | |||||
Applicable load (resistive load:
AC1 class) *2 |
5.1 kW
(at 200 VAC) |
8.6 kW
(at 200 VAC) |
12.1 kW
(at 200 VAC) |
15.5 kW
(at 200 VAC) |
Model | G3PE-
515B- 3(N) |
G3PE-
515B- 2(N) |
G3PE-
525B- 3(N) |
G3PE-
525B- 2(N) |
G3PE-
535B- 3(N) |
G3PE-
535B- 2(N) |
G3PE-
545B- 3(N) |
G3PE-
545B- 2(N) |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 200 to 480 VAC | |||||||
Operating voltage range | 180 to 528 VAC | |||||||
Rated load current *1 | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.5 A | |||||||
Inrush current resistance
(peak value) |
220 A
(60 Hz, 1 cycle) |
440 A
(60 Hz, 1 cycle) |
||||||
Permissible I2t (reference value) | 260A2s | 1,260A2s | ||||||
Applicable load (resistive load:
AC1 class) *2 |
12.5 kW
(at 480 VAC) |
20.7 kW
(at 480 VAC) |
29.0 kW
(at 480 VAC) |
37.4 kW
(at 480 VAC) |
Model | G3PE-
215B- 3H |
G3PE-
215B- 2H |
G3PE-
225B- 3HH |
G3PE-
225B- 2H |
G3PE-
235B- 3H |
G3PE-
235B- 2H |
G3PE-
245B- 3H |
G3PE-
245B- 2H |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 100 to 240 VAC | |||||||
Operating voltage range | 75 to 264 VAC | |||||||
Rated load current * | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.2 A | 0.5 A | ||||||
Inrush current resistance
(peak value) |
150 A
(60 Hz, 1 cycle) |
220 A
(60 Hz, 1 cycle) |
440 A
(60 Hz, 1 cycle) |
|||||
Permissible I2t (reference value) | 121A2s | 260A2s | 1,260A2s | |||||
Applicable load (resistive load:
AC1 class) |
Refer to Engineering Data on Data Sheet. |
Model | G3PE-
515B- 3H |
G3PE-
515B- 2H |
G3PE-
525B- 3H |
G3PE-
525B- 2H |
G3PE-
535B- 3H |
G3PE-
535B- 2H |
G3PE-
545B- 3H |
G3PE-
545B- 2H |
---|---|---|---|---|---|---|---|---|
Rated load voltage | 200 to 480 VAC | |||||||
Operating voltage range | 180 to 528 VAC | |||||||
Rated load current * | 15 A (at 40 ° C) | 25 A (at 40 ° C) | 35 A (at 25 ° C) | 45 A (at 25 ° C) | ||||
Minimum load current | 0.5 A | |||||||
Inrush current resistance
(peak value) |
220 A
(60 Hz, 1 cycle) |
440 A
(60 Hz, 1 cycle) |
||||||
Permissible I2t (reference value) | 260A2s | 1,260A2s | ||||||
Applicable load (resistive load:
AC1 class) |
Refer to Engineering Data on Data Sheet. |
Model |
G3PE- 215B- 3(N) |
G3PE- 215B- 2(N) |
G3PE- 225B- 3(N) |
G3PE- 225B- 2(N) |
G3PE- 235B- 3(N) |
G3PE- 235B- 2(N) |
G3PE- 245B- 3(N) |
G3PE- 245B- 2(N) |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop |
1.6 V (RMS) max. | |||||||
Leakage current * | 10 mA max. (at 200 VAC) | |||||||
Insulation resistance |
100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance |
DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude) Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) |
|||||||
Shock resistance | 294 m/s2 (reverse mounting: 98 m/s2) | |||||||
Ambient storage temperature |
- 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature |
- 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity |
45% to 85% | |||||||
Weight | Approx. 1.25 kg | Approx. 1.45 kg |
Approx. 1.25 kg |
Approx. 1.65 kg |
Approx. 1.45 kg |
Approx. 2.0 kg |
Approx. 1.65 kg |
Model |
G3PE- 515B- 3(N) |
G3PE- 515B- 2(N) |
G3PE- 525B- 3(N) |
G3PE- 525B- 2(N) |
G3PE- 535B- 3(N) |
G3PE- 535B- 2(N) |
G3PE- 545B- 3(N) |
G3PE- 545B- 2(N) |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop |
1.8 V (RMS) max. | |||||||
Leakage current * | 20 mA max. (at 480 VAC) | |||||||
Insulation resistance |
100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance |
DIN Track mounting: 10 to 55 to 10 Hz, 0.175-mm single amplitude (0.35-mm double amplitude) Screw mounting: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) |
|||||||
Shock resistance | 294 m/s2 (reverse mounting: 98 m/s2) | |||||||
Ambient storage temperature |
- 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature |
- 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity |
45% to 85% | |||||||
Weight | Approx. 1.25 kg | Approx. 1.45 kg |
Approx. 1.25 kg |
Approx. 1.65 kg |
Approx. 1.45 kg |
Approx. 2.0 kg |
Approx. 1.65 kg |
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
Model | G3PE-
215B- 3H |
G3PE-
215B- 2H |
G3PE-
225B- 3H |
G3PE-
225B- 2H |
G3PE-
235B- 3H |
G3PE-
235B- 2H |
G3PE-
245B- 3H |
G3PE-
245B- 2H |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.6 V (RMS) max. | |||||||
Leakage current * | 10 mA max. (at 200 VAC) | |||||||
Insulation resistance | 100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||||||
Shock resistance | Destruction: 294 m/s2 | |||||||
Ambient storage temperature | - 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature | - 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 300 g |
Model | G3PE-
515B- 3H |
G3PE-
515B- 2H |
G3PE-
525B- 3H |
G3PE-
525B- 2H |
G3PE-
535B- 3H |
G3PE-
535B- 2H |
G3PE-
545B- 3H |
G3PE-
545B- 2H |
---|---|---|---|---|---|---|---|---|
Operate time | 1/2 of load power source cycle + 1 ms max. | |||||||
Release time | 1/2 of load power source cycle + 1 ms max. | |||||||
Output ON voltage drop | 1.8 V (RMS) max. | |||||||
Leakage current * | 20 mA max. (at 480 VAC) | |||||||
Insulation resistance | 100 M Ω min. (at 500 VDC) | |||||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min | |||||||
Vibration resistance | 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude) | |||||||
Shock resistance | Destruction: 294 m/s2 | |||||||
Ambient storage temperature | - 30 to 100 ° C (with no icing or condensation) | |||||||
Ambient operating temperature | - 30 to 80 ° C (with no icing or condensation) | |||||||
Ambient operating humidity | 45% to 85% | |||||||
Weight | Approx. 300 g |
* The leakage current of phase S will be approximately √3 times larger if the 2-element model is used.
Model | Weight |
---|---|
Y92B-P50 | Approx. 450 g |
Y92B-P100 | Approx. 450 g |
Y92B-P150 | Approx. 600 g |
Y92B-P200 | Approx. 850 g |
Y92B-P250 | Approx. 1,200 g |
last update: September 24, 2012