Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

H3M

Solid-state Timer

H3M

Solid-state Timer with Variable Time Ranges

about this Product Family

Time Ranges

Four time ranges are available for each timer by changing the time range selector switch positions to different combinations.

Time range code Time range selector switch
A 0.05 to 0.5 s 0.5 to 5 s 0.05 to 0.5 min 0.5 to 5 min
B 0.1 to 1 s 1 to 10 s 0.1 to 1 min 1 to 10 min
C 0.3 to 3 s 3 to 30 s 0.3 to 3 min 3 to 30 min

Time range code Time multiplying key
D 0.1 to 1 min 1 to 10 min 0.1 to 1 hrs 1 to 10 hrs
E 0.3 to 3 min 3 to 30 min 0.3 to 3 hrs 3 to 30 hrs

Ratings

Rated supply voltage 100/110/120 VAC (50/60 Hz), 200/220/240 VAC (50/60 Hz),
12, 24, 48, 100, 110 VDC *2
Operating voltage range AC: 85% to 110% of rated supply voltage
DC: 80% to 110% of rated supply voltage *3
Power consumption AC: Approx. 5 VA/2 W
DC: Approx. 2 W
Control outputs 5 A at 250 VAC, resistive load (cosφ = 1)

*1. Color indicators for the rated voltage are provided on the front of the Timer.
       Blue: 100/110/120 VAC
       Red: 200/220/240 VAC
       None: Other voltages
*2. With DC ratings, single-phase full-wave rectified power sources may be used.
*3. 90% to 110% for 12-VDC models.

Characteristics

Accuracy of operating
time
±1% max. *
Setting error ±10% max.
Reset time 0.1 s max.
Influence of voltage ±1% max. *
Influence of temperature ±2% max. *
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts)
1,500 VAC, 50/60 Hz for 1 min (between contact and control circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Destruction: 10 to 55 Hz with 0.75-mm double amplitude
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude
Shock resistance Destruction: 1,000 m/s2 (approx. 100 G)
Malfunction: 100 m/s2 (approx. 10 G)
Ambient temperature Operating: -10°C to 50°C
Storage: -25°C to 65°C
Ambient humidity Operating: 35% to 85%
Life expectancy Mechanical: 20,000,000 operations min. (under no load at 1,800 operations/h)
Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h)
Approved standards UL (File No. E41515), CSA (File No. LR22310)
Weight Approx. 100 g

* For the timer with time range code A, add ±10 ms to the respective characteristics when the time range selector
  switches are in the x 1 s (0.05 to 0.5 s) position.