CSA 22.2 No. 14, EN 60947-4-3, UL508 (The G3PF-2[][]B-[][][] Series)
Solid State Relays with Built-in Current Transformer
about this Product Family
last update: September 24, 2012
CSA 22.2 No. 14, EN 60947-4-3, UL508 (The G3PF-2[][]B-[][][] Series)
Rated power supply voltage | 24 VDC |
---|---|
Operating voltage range | 20.4 to 26.4 VDC |
Current consumption | 50 mA DC max. (at 24 VDC) |
Output OFF collector voltage | 30 VDC max. |
---|---|
Maximum carry current | 100 mA |
Output form | NPN open collector (ON when error is detected.) |
Minimum load current | 0.1 mA |
Input method | Voltage input |
---|---|
Rated input voltage | 12 to 24 VDC |
Operating input voltage range | 9.6 to 26.4 VDC |
Operate voltage | 9.6 VDC max. |
Release voltage | 1.0 VDC min. |
Input current | 5 mA DC max. (at 12 VDC) 10 mA DC max. (at 24 VDC) |
Model | G3PF-225B | G3PF-235B | G3PF-525B | G3PF-535B |
---|---|---|---|---|
G3PF-225B-CTB | G3PF-235B-CTB | G3PF-525B-CTB | G3PF-535B-CTB | |
G3PF-225B-STB | G3PF-235B-STB | G3PF-525B-STB | G3PF-535B-STB | |
Rated load voltage | 100 to 240 VAC (50/60 Hz) | 200 to 480 VAC (50/60 Hz) | ||
Operating voltage range | 75 to 264 VAC, 50/60 Hz | 180 to 528 VAC, 50/60 Hz | ||
Applicable load current * | 25 A (at 40°C) | 35 A (at 40°C) | 25 A (at 40°C) | 35 A (at 40°C) |
Minimum load current | 2 A | |||
Inrush current resistance | 220 A (60 Hz, 1 cycle) | 430 A (60 Hz, 1 cycle) | 220 A (60 Hz, 1 cycle) | 430 A (60 Hz, 1 cycle) |
Model | G3PF-225B | G3PF-235B | G3PF-525B | G3PF-535B | |
---|---|---|---|---|---|
G3PF-225B-CTB | G3PF-235B-CTB | G3PF-525B-CTB | G3PF-535B-CTB | ||
G3PF-225B-STB | G3PF-235B-STB | G3PF-525B-STB | G3PF-535B-STB | ||
Operate time | 1/2 of load power source cycle + 1 ms max. | ||||
Release time | 1/2 of load power source cycle + 1 ms max. | ||||
Main circuit | Output ON voltage drop | 1.6 V (RMS) max. | 1.8 V (RMS) max. | ||
Leakage current | 10 mA max. (at 200 VAC) | 20 mA max. (at 480 VAC) | |||
Alarm output | Output ON voltage drop | 1.5 V max. | |||
Leakage current | 1 mA max. | ||||
Isolation resistance | 100 MΩ min. (at 500 VDC) | ||||
Dielectric strength | 2,500 VAC, 50/60 Hz for 1 min. | ||||
Vibration resistance | Destruction: 10 to 55 to10 Hz, 0.35-mm single amplitude (0.7-mm double amplitude) | ||||
Shock resistance | Destruction: 294 m/s2 | ||||
Ambient storage temperature | -30 to 70°C (with no icing or condensation) | ||||
Ambient operating temperature | -20 to 60°C (with no icing or condensation) | ||||
Ambient operating humidity | 45% to 85% | ||||
Weight | Approx. 400 g | Approx. 630 g | Approx. 400 g | Approx. 630 g |
last update: September 24, 2012