Page top

Building Automation


Industrial Automation


Power Automation & Safety

Bangladesh Distributor

CRT1B-[]D02S(-1)

Bit Slave Units with e-CON Connectors

CRT1B-[]D02S(-1)

Simple and Intelligent Bit Slaves with Industry-standard e-CON connectors.

about this Product Family

Basic Performance Specifications

Item Specification
Communications power supply voltage 14 to 26.4 VDC
I/O power supply voltage *1 20.4 to 26.4 VDC (24 VDC -15%/+10%)
Noise immunity Conforms to IEC 61000-4-4, 2 kV (power line).
Vibration resistance 10 to 60 Hz with double-amplitude of 0.7 mm, 60 to 150 Hz and 50 m/s2 in X, Y, and Z
directions for 80 min each
Shock resistance 150 m/s2 (3 times each in 6 directions on 3 axes)
Dielectric strength 500 VAC (between isolated circuits)
Insulation resistance 20 MΩ min. (between isolated circuits)
Ambient operating temperature -10 to 55°C
Ambient operating humidity 25% to 85% (with no condensation)
Ambient operating atmosphere No corrosive gases
Storage temperature -25 to 65°C
Storage humidity 25% to 85% (with no condensation)
Terminal block screw tightening torque *2 M3 wiring screws: 0.5 Nm
M3 mounting screws: 0.5 Nm
Installation Mounted on 35-mm DIN Track or Mounting Bracket, or secured with M4 screws
(depending on model)

*1 The I/O power supply is called the sensor power supply in information for the CRT1-VAD04S.
*2 Applicable only to Slaves to which screw terminal blocks are mounted.

Input Section Specifications

Item Specification
Model CRT1B-ID02S CRT1B-ID02S-1
I/O capacity 2 inputs
Internal I/O common NPN PNP
ON voltage 10.5 VDC min. (between each input terminal
and the V terminal)
10.5 VDC min. (between each input terminal
and the G terminal)
OFF voltage 5 VDC max. (between each input terminal and
the V terminal)
5 VDC max. (between each input terminal and
the G terminal)
OFF current 1.0 mA max.
Input current 3.0 mA max./input (at 10.5 VDC)
Sensor power supply voltage Communications power supply voltage + 0 V (max.)
Communications power supply voltage - 1 V (min.)
ON delay 1.5 ms max.
OFF delay 1.5 ms max.
Number of circuits per common 2 inputs/common
Power short-circuit detection Supported
Isolation method No isolation
Input indicators LEDs (yellow)
Degree of protection IEC standard IP20
Installation Screw installation (M4)
Power supply type Network power supply
Communications power supply
current consumption *
65 mA max. for 24-VDC power supply voltage
80 mA max. for 14-VDC power supply voltage
45 mA max. for 24-VDC power supply voltage
65 mA max. for 14-VDC power supply voltage
Weight 70 g max.

* The current consumption is for Bit Slave Unit communications current when all inputs are OFF, i.e., it does not include
   input device current consumption. The communications power supply is also used for the I/O power supply for sensors.
   Be sure to consider the sensor current consumption and the number of sensors connected in addition to the
   communications power.
   The power supply current consumption is expressed by the following formula.
   Communications power supply current consumption = Bit Slave Unit communications current consumption + (Bit Slave
   Unit input current x number of inputs used) + (sensor current consumption x number of sensors used)

Output Section Specifications

Item Specification
Model CRT1B-OD02S CRT1B-OD02S-1
I/O capacity 2 outputs
Internal I/O common NPN PNP
Rated output current 0.2 A/output
Load power supply voltage Communications power supply voltage + 0 V (max.)
Communications power supply voltage - 1.2 V (min.)
Residual voltage 1.2 V max. (0.2 A DC, between each output
terminal and the BS-
1.2 V max. (0.2 A DC, between each output
terminal and the BS+
Leakage current 0.1 mA max.
ON delay 0.5 ms max.
1.5 ms max.
OFF delay
Number of circuits per common 2 outputs/common
Load power short-circuit detection Supported
Isolation method No isolation
Output indicators LEDs (yellow)
Degree of protection IEC standard IP20
Installation Screw installation (M4)
Power supply type Network power supply
Communications power supply
current consumption *
55 mA max. for 24-VDC power supply voltage
75 mA max. for 14-VDC power supply voltage
55 mA max. for 24-VDC power supply voltage
70 mA max. for 14-VDC power supply voltage
Weight 59 g max.

* The current consumption is for Bit Slave Unit communications current when all outputs are OFF, i.e., it does not include
   output device load current consumption. The communications power supply is also used for the I/O power supply for
   actuators. Be sure to consider the actuator load current consumption and the number of actuators connected in addition
   to the communications power.
   The power supply current consumption is expressed by the following formula.
   Communications power supply current consumption = Bit Slave Unit communications current consumption + (Bit Slave
   Unit input current x number of inputs used) + (actuator load current x number of actuators used)