Efficiency (typical) | 80% min. | ||
---|---|---|---|
Input | Voltage | 100 to 240 VAC (85 to 264 VAC), 95 to 350 VDC *1 | |
Frequency | 50/60 Hz (47 to 450 Hz) | ||
Current | 100 VAC input | 0.8 A max. | |
200 VAC input | 0.45 A max. | ||
Leakage current |
100 VAC input | 0.4 mA max. | |
200 VAC input | 0.75 mA max. | ||
Inrush current *2 |
100 VAC input | 25 A max. | |
200 VAC input | 50 A max. | ||
Output | Voltage adjustment range *3 | -10 to 15% (with V.ADJ) of rated output voltage | |
Ripple | 2% (p-p) max. (-25 to -10°C: 4% max.) | ||
Input variation influence | 0.5% max. | ||
Load variation influence (rated input voltage) |
1.5% max. | ||
Temperature variation influence | 0.05%/°C max. | ||
Start up time *2 | 1,000 ms max. (100 VAC or 200 VAC, at rated output voltage) | ||
Hold time *2 | 15 ms min., 20 ms (typical) (100 VAC or 200 VAC, at rated output voltage) | ||
Additional functions |
Overload protection *2 | 105% to 135% of rated load current, inverted L drop, intermittent, automatic reset | |
Parallel operation | Yes (2 units max. For details, refer to the derating curve in Engineering Data on Data Sheet. For DC input, parallel operation is possible only for 110 to 350 VDC.) |
||
Series operation | No | ||
Others | Ambient temperature | Operating: Refer to the derating curve in Engineering Data on Data Sheet. (with no icing or condensation) Storage: -25 to 75°C (with no icing or condensation) |
|
Ambient humidity | Operating: 10 to 90% Storage: 10 to 90% |
||
Mounting method | DIN track mounting, surface mounting | ||
Dielectric strength | 2.0 kVAC for 1 min. (between all inputs and exposed non-current-carrying metal parts; detection current: 10 mA max.) 3.0 kVAC for 1 min. (between all inputs and all outputs; detection current: 20 mA max.) 1.0 kVAC for 1 min. (between all outputs and non-current-carrying metal parts; detection current: 10 mA max.) |
||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs/exposed non-current-carrying metal parts) at 500 VDC |
||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z direction | ||
Shock resistance | 300 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||
Output indicator | Yes (color: green) | ||
EMI | Conducted emissions | Conforms to EN61000-6-3 (Class B) | |
Radiated emissions | Conforms to EN61000-6-3 (Class B) | ||
Approved standards | UL: UL508 (listing, Class 2: Per UL1310), UL60950-1, UL1604 (Class I/Division 2) cUL: CSA C22.2 No. 14 (listing, Class2: Per CSA C22.2 No. 223), CSA C22.2 No. 213 (Class I/Division 2) cUR: CSA C22.2 No.60950-1 EN/VDE: EN60950-1 (=VDE 0805 Teil 1), EN50178 (=VDE 0160) |
||
Weight | 240 g max. |