Supply voltage | 100 to 240 VAC, 50/60 Hz
24 VAC, 50/60 Hz; 24 VDC |
|
---|---|---|
Operating voltage range | 85% to 110% of rated supply voltage | |
Power consumption | 100 to 240 VAC: 5 VA
24 VAC: 3 VA, 24 VDC: 2 W |
|
Sensor input | Thermocouple input type: K, J, L
Platinum resistance thermometer input type: Pt100, JPt100 Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100 |
|
Control
output |
Relay output | SPST-NO, 250 VAC, 3A (resistive load) |
Voltage output
(for driving the SSR) |
12 VDC, 21 mA (with short-circuit protection circuit) | |
Control method | ON/OFF or 2-PID (with auto-tuning) | |
Alarm output | SPST-NO, 250 VAC, 1A (resistive load) | |
Setting method | Digital setting using front panel keys | |
Indication method | 7-segment digital display (character height: 13.5 mm) and deviation indicators | |
Other functions | Setting change prohibit (key protection)
Input shift Temperature unit change (°C/°F) Direct/reverse operation Temperature range, Sensor switching (K/J/L, Pt100/JPt100) Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models. Control period switching 8-mode alarm output Sensor error detection |
|
Ambient operating
temperature |
-10 to 55°C (with no condensation or icing); with 3-year guarantee: -10 to 50°C | |
Ambient operating humidity | 25% to 85% | |
Storage temperature | -25 to 65°C (with no condensation or icing) |
2. Models for 24 VAC/DC can also be manufactured.