Power rating | 15 W | 30 W | 50 W | 100 W | 150 W | ||
---|---|---|---|---|---|---|---|
Efficiency | 5-V models | 75% min. | 75% min. | 80% min. | 81% min. | 81% min. | |
12-V models | 78% min. | 79% min. | 79% min. | 81% min. | 81% min. | ||
15-V models | 78% min. | 79% min. | 79% min. | 81% min. | 81% min. | ||
24-V models | 80% min. | 81% min. | 80% min. | 82% min. | 83% min. | ||
Input | Voltage *1 | 100 to 240 VAC (85 to 265 VAC) | |||||
Frequency *1 | 50/60 Hz (47 to 63 Hz) | ||||||
Current | 100-V input | 0.5 A max. | 0.9 A max. | 0.8 A max. | 1.4 A max. | 2.0 A max. | |
200-V input | 0.25 A max. | 0.45 A max. | 0.4 A max. | 0.7 A max. | 1.0 A max. | ||
Power
factor |
100-V input | --- | 0.98 min. | ||||
200-V input | --- | 0.94 min. | |||||
Harmonic current
emissions |
--- | Conforms to EN 61000-3-2 | |||||
Leakage
current |
100-V input | 0.4 mA max. (at rated output) | |||||
200-V input | 0.75 mA max. (at rated output) | ||||||
Inrush
current *2 |
100-V input | 17.5 A max. (for cold start at 25 °C) | |||||
200-V input | 35 A max. (for cold start at 25 °C) | ||||||
Output | Voltage adjustment
range *3 |
-20% to 20% (with V. ADJ) (S8VM-[][][]24A[]/P[]: -10% to 20%) | |||||
Ripple | 3.2% (p-p) max. (5 V),
1.5% (p-p) max. (12 V), 1.2% (p-p) max. (15 V), 1.0% (p-p) max. (24 V), (at rated input/output voltage) |
3.2% (p-p) max. (5 V),
1.5% (p-p) max. (12 V), 1.2% (p-p) max. (15 V), 0.75% (p-p) max. (24 V), (at rated input/output voltage) |
|||||
Input variation influence | 0.4% max. (at 85 to 265 VAC input, 100%) | ||||||
Load variation influence
(rated input voltage) |
0.8% max. (with rated input, 0 to 100% load) | ||||||
Temperature variation
influence |
0.02%/°C max. | ||||||
Startup time *2 | 1,100 ms max. (at rated
input/output voltage) |
800 ms max. (at rated input/output voltage) | |||||
Hold time *2 | 20 ms typ. (15 ms min.) (at rated input/output voltage) | ||||||
Additional
functions |
Overload protection *2 | 105% to 160% of rated load
current, voltage drop, intermittent, automatic reset |
105% to 160% of rated load current,
voltage drop (12 V, 15 V, and 24 V), voltage drop, intermittent (5 V), automatic reset |
||||
Overvoltage protection
*2 |
Yes *4 | ||||||
Undervoltage alarm
indication |
Yes (color: Yellow (DC LOW1), red (DC LOW2)) (S8VM-[][][]24A[]/P[] only) | ||||||
Undervoltage alarm output | No | Yes (S8VM-[][][]24A[]/P[] only) (Transistor
output), 30 VDC max., 50 mA max. *8 |
|||||
Series operation | Yes for up to 2 Power Supplies (with external diode) | ||||||
Parallel operation | No (However, backup operation is possible. An external diode is required.) | ||||||
Remote sensing function | No | Yes | |||||
Other | Ambient operating
temperature |
Refer to the derating curve in See Engineering Data on Data Sheet (15-W,
30-W, 50-W, 100-W, 150-W Models). (with no icing or condensation) *2 |
|||||
Storage temperature | -25 to 65°C | ||||||
Ambient operating
humidity |
30% to 85% (Storage humidity: 25% to 90%) | ||||||
Dielectric strength | 3.0 kVAC for 1 min. (between all inputs and outputs; detection current: 20
mA) 2.0 kVAC for 1 min. (between all inputs and PE/FG terminals; detection current: 20 mA) 500 VAC for 1 min. (between all outputs and PE/FG terminals; detection current: 100 mA) 500 VAC for 1 min. (between all outputs (except the detection output terminals) and detection output terminals; detection current: 20 mA) (S8VM- [][][]24A[]/P[] only) |
||||||
Insulation resistance | 100 MΩ min. (between all outputs and all inputs, PE/FG terminals) at 500
VDC |
||||||
Vibration resistance | 10 to 55 Hz, 0.375-mm single amplitude for 2 hours each in X, Y, and Z
directions |
||||||
Shock resistance | 150 m/s2, 3 times each in ±X, ±Y, ±Z directions | ||||||
Output indicator | Yes (color: Green) | ||||||
EMI | Conducted
Emission |
Conforms to EN55011 Group1 Class B and based on FCC Class B *5 | |||||
Radiated
Emission |
Conforms to EN55011 Group1 Class B *6 | ||||||
EMS | Conforms to EN61204-3 High severity levels | ||||||
Approved
standards |
UL | UL508 (Listing), UL60950-1 | |||||
cUL | CSA C22.2 No.14 | ||||||
cUR | CSA No. 60950-1 | ||||||
EN/TÜV | EN50178, EN60950-1
SELV (EN60950-1) According to VDE0160/P100 |
||||||
SEMI | SEMI F47-0200 (200 VAC input) | ||||||
Weight *7 | 180 g max. | 220 g max. | 290 g max. | 460 g max. | 530 g max. |