Series | NS5-V2 | NS8-V2 | NS10-V2 | NS12-V2 | NS15-V2 |
---|---|---|---|---|---|
Rated power supply
voltage |
24 VDC | ||||
Allowable voltage range | 20.4 to 27.6 VDC (24 VDC ± 15%) | ||||
Power consumption | 15 W max. | 25 W max. | 45 W max. | ||
Ambient operating
temperature |
0 to 50 °C
Note: The ambient operating temperature is subject to the following restrictions according to the mounting angle. Mounting angle of 0 to 30° to the horizontal: When no Expansion Units are mounted, the operating temperature range is 0 to 45 °C. When a Video Input Unit or a Controller Link Interface Unit is mounted, the ambient operating temperature is 0 to 35 °C. Mounting angle of 30 to 90 ° to the horizontal: Operating temperature range of 0 to 50 °C |
||||
Storage temperature | -20 to 60 °C *1 | ||||
Ambient operating
humidity |
35 to 85% (0 to 40 °C), 35 to 60% (40 to 50 °C) (with no condensation) | ||||
Operating environment | No corrosive gases. | ||||
Noise immunity | Conforms to IEC61000-4-4, 2 kV (power lines). | ||||
Vibration resistance
(during operation) |
10 to 57 Hz, 0.075 mm amplitude, 57 to 150 Hz, 9.8
m/s2 30 min each in X, Y, and Z directions |
5 to 8.4 Hz, 3.5 mm single amplitude,
8.4 to 150 Hz, 9.8 m/s2 10 min times each in X, Y, and Z directions |
|||
Shock resistance
(during operation) |
147 m/s2 3 times each in direction of X, Y, and Z | ||||
Weight | 1.0 kg max. | 2.0 kg max. | 2.3 kg max. | 2.5 kg max. | 4.2 kg max. |
Degree of protection | Front operating panel: IP65 oil-proof type and NEMA4 UL type 4. *2
May not be applicable in locations with long-term exposure to oil. |
||||
Ground | Ground to 100 Ω or less. | ||||
Battery life | 5 years (at 25 °C): Replace battery within 5 days after the battery runs low (indicator lights
orange). |
||||