Items | Specifications |
---|---|
Model | CJ1W-CLK23 3G8F7-CLK23-E CJ1W-CLK21-V1 *1 3G8F7-CLK21-EV1 *1 |
Type | Wired (shielded twisted-pair cable) |
Communications method | N:N token-bus method |
Code | Manchester code |
Modulation | Baseband code |
Synchronization | Flag synchronization (conforms to HDLC frames) |
Transmission path format | Multidrop method (bus type) |
Transmission speed | The following are the maximum transmission distances depending on the transmission speed. 2 Mbits/s: 500 m 1 Mbits/s: 800 m 500 kbits/s: 1 km |
Maximum transmission distance |
|
Maximum distance between nodes |
Not specified. (Maximum transmission distance must be satisfied for the entire system.) |
Medium | Specified shielded twist-pair cable Two signal wires, one shield |
Node connection method | PLC: Connection to terminal block Computer: Connection using special (supplied) connector |
Maximum number of nodes | 32 or 62 nodes *2 *3 |
Applicable Programming Devices |
CX-Integrator in CX-One, CX-Net in CX-Programmer *3, and Programming Console |
Communications functions | Data links and message service |
Number of data link words | Send words per node: 4,000 words max. (CJ1W-CLK[]3), 1,000 words max. (All other Units) Number of send/receive words per node: 12,000 words max. (Pre-Ver. 1.2) 20,000 words max. (unit Ver. 1.2 or later) Total number of send words per network: 62,000 words max. |
Data link areas | PLC: Bit areas (CIO Area, Work Area, Link Area *4), Data Memory (DM), Extended DM Area (EM) Computer: FinsGateway event memory |
Message length | 2,012 bytes max. (including the header) |
RAS functions | Polling node backup function Self-diagnosis function (hardware checking at startup) Echoback test and broadcast test (using the FINS command) Watchdog timer Error log function |
Error control | Manchester code check CRC check (CCITT X16 +X12 +X5 +1) |