Conductive Level Controller
Type |
Float-less level controller, DC power supply type Compact Plug-in model |
---|---|
Controlling materials |
Ordinary purified water or sewage water |
As of October 10, 2016
Type | Float-less level controller, DC power supply type Compact Plug-in model |
---|---|
Controlling materials | Ordinary purified water or sewage water |
Rated supply voltage | 24 VDC |
Operating voltage range | 85 to 110% of rated voltage |
Power consumption | Approx. 2 W max. |
Interelectrod voltage | 5 VAC p-p |
Response time | Operate: 1.5 s Max. Release: 3.0 s Max. |
Wiring distance | Cable length: 100 m Max. The length when using completely-insulated 600 V, 3-conductor (0.75 mm**2) VCT cables. |
Ambient temperature | Operating: -10 to 55 ℃ Storage: -10 to 55 ℃ |
Ambient humidity | Operating: 45 to 85%RH Storage: 45 to 85%RH |
Insulation resistance | Between power terminals and Electrode terminals: 100 MOhm Min. (at 500 VDC) Between power terminals and contact terminals: 100 MOhm Min. (at 500 VDC) Between Electrode terminals and contact terminals: 100 MOhm Min. (at 500 VDC) |
Dielectric strength | Between power terminals and Electrode terminals: 2,000 VAC 50/60 Hz for 1min Between power terminals and contact terminals: 2,000 VAC 50/60 Hz for 1min Between Electrode terminals and contact terminals: 2,000 VAC 50/60 Hz for 1min |
Vibration resistance | 10 to 55 Hz, 1.5-mm double amplitude |
Shock resistance | 150 m/s**2 |
Life expectancy | Electrical: 70,000 operations Min. Mechanical: 20,000,000 operations Min. |
Display | On detection: OUT LED (red) [ON] |
Sockets | PF113A PL11 |
Accessories | Instruction Manual, Mounting bracket |
Weight | Approx. 155 g |
As of October 10, 2016
As of October 10, 2016
As of October 10, 2016
Series