Solid State Relays G3[]-VD
Product classification |
Relay compatible Solid State Relay |
---|---|
Operating rated voltage |
100 to 110 VAC |
Output form |
SPST-NO |
Load voltage range |
75 to 264 VAC 50/60 Hz |
Load current |
AC: 0.1 A to 2 A at 40 CEL |
Zero cross function |
Equipped |
Indicator |
Equipped |
Terminal structure |
Plug-in |
As of September 9, 2016
Product classification | Relay compatible Solid State Relay |
---|---|
Operating rated voltage | 100 to 110 VAC |
Operating voltage range | 75 to 125 VAC |
Input impedance | 41 kOhm+/- 20% at 25 CEL |
Must operate voltage | 75VAC max. |
Must release voltage | 20VAC min. |
Isolation | Photocoupler |
Output form | SPST-NO |
Rated load voltage | 100 to 240VAC 50/60 Hz |
Load voltage range | 75 to 264 VAC 50/60 Hz |
Load current | AC: 0.1 A to 2 A at 40 CEL |
Inrush current resistivity | AC: 45 A (60 Hz, 1 cycle) |
Output ON voltage drop | 1.6 V (RMS) |
Leakage current | 5 mA (at 100 VAC) 10 mA (at 200 VAC) |
Ambient temperature | Operating: -30 to 80 ℃ Storage: -30 to 100 ℃ (_with no icing or condensation) |
Ambient humidity | Operating: 45 to 85%RH (_with no icing or condensation) |
Operate time | 3/2 cycle of load power source + 1 ms Max. |
Release time | 3/2 cycle of load power source + 1 ms Max. |
Protection for output | Snubber |
Zero cross function | Equipped |
Indicator | Equipped |
Insulation resistance | Between input to output: at 500 VDC |
Dielectric strength | Between input to output: 1500 V |
Vibration resistance | 10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude) in each 3 directions for 2 hours |
Shock resistance | 1000 m/s**2, in each 6 directions 3 times |
Terminal structure | Plug-in |
Mounting | Socket |
Weight | Approx.50 g |
As of September 9, 2016
As of September 9, 2016
As of September 9, 2016
As of September 9, 2016
Terminal arrangement and internal connection
As of September 9, 2016
As of September 9, 2016
Load current-ambient temperature
Inrush current resistivity (Non-repetitive) (The dotted line is a repetition. Keep the inrush current below the values shown by the dotted line if it occurs repetitively.)
As of September 9, 2016
Series