Power Relay
Coil ratings |
100 VDC 17 mA 110 VDC 19 mA |
---|---|
Operating indicator |
Not equipped |
Coil surge killer |
Not equipped |
Contact type |
DPDT |
Contact method |
Single |
Contact material |
Contact body: Ag Contact finish: Nothing |
Contact rated load |
110 VDC 10 A (Resistive load) 110 VDC 7 A (Inductive load (L/R = 7 ms)) |
Maximum switching current |
AC: 15 A DC: 15 A |
Terminal structure |
Solder terminal |
As of September 9, 2016
Product classification | Monostable relays DC-switching type |
---|---|
Coil ratings | 100 VDC 17 mA 110 VDC 19 mA |
Coil resistance | 5750 Ω |
Operate voltage (Set voltage) | 70 % max. |
Release voltage (Reset voltage) | 10 % min. |
Max. voltage | 110 % (of rated voltage) |
Power consumption | 2.1 W max. |
Operating indicator | Not equipped |
Coil surge killer | Not equipped |
Contact type | DPDT |
Contact method | Single |
Contact material | Contact body: Ag Contact finish: Nothing |
Contact rated load | 110 VDC 10 A (Resistive load) 110 VDC 7 A (Inductive load (L/R = 7 ms)) |
Maximum switching voltage | 250 VAC 250 VDC (Resistive load) |
Maximum switching current | AC: 15 A DC: 15 A |
Maximum switching power | DC: 1200 W (Resistive load) DC: 800 W (Inductive load (L/R = 7 ms)) |
Failure rate | 10 mA at 5 VDC (failure level: P Reference value) |
Ambient temperature (Operating) | -10 to 55 ℃ (with no icing or condensation) |
Ambient_humidity (Operating) | 5 to 85%RH (with no icing or condensation) |
Contact resistance | 25 mΩ max., Measuring the voltage drop across the contacts by applying test voltage/current as 5 VDC 1 A |
Operating time (set time) | 50 ms |
Release time (Reset time) | 30 ms |
Max.operating frequency (Mechanical) | 7200 |
Max.operating frequency (Erectrical) | 1800 opn./h |
Insulation resistance | Between coil and contacts: 100 MΩ min. (at 500 VDC) Between contacts of different polarity: 100 MΩ min. (at 500 VDC) Between contacts of same polarity: 100 MΩ min. (at 500 VDC) Between current-carrying metal parts and ground terminal: 100 MΩ min. (at 500 VDC) |
Dielectric strength | Between coil and contacts: 2000 V (50/60 Hz 1 min) Between contacts of different polarity: 2000 V (50/60 Hz 1 min) Between contacts of same polarity: 1500 V (50/60 Hz 1 min) Between current-carrying metal parts and ground terminal: 2000 V (50/60 Hz 1 min) |
Vibration resistance (Destruction) | 10 to 55 to 10 Hz, 0.75-mm single amplitude |
Vibration resistance (Malfunction) | 10 to 50 to 10 Hz, 0.5-mm single amplitude |
Shock resistance (Destruction) | 1000 m/s**2 |
Shock resistance (Malfunction) | 100 m/s**2 |
Endurance (Mechanical) | 5,000,000 operations min. |
Endurance (Electrical) | 500,000 operations min. |
Protective structure | Open coils |
Terminal structure | Solder terminal |
Weight | Approx.165 g |
As of September 9, 2016
As of September 9, 2016
As of September 9, 2016
As of September 9, 2016
Electrical life
As of September 9, 2016
about this Product