Switch Mode Power Supply (15/30/60/90/120/180/240/480-W Models)
Power rating |
30 W |
---|---|
Rated input voltage |
100 to 240 VAC |
Output voltage |
24 VDC |
Heat radiation |
Natural air-cooling |
Construction |
Covered type |
Terminal type |
Screw terminal |
Mounting type |
DIN Rail mounting type |
As of October 10, 2016
Power rating | 30 W |
---|---|
Efficiency | 85% TYP.(At 100 VAC input) 86% TYP.(At 200 VAC input) |
Rated input voltage | 100 to 240 VAC |
Allowable input voltage variable range | 85 to 264 VAC 80 to 370 VDC |
Note at DC input | The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). |
Frequency | 50/60 Hz(47 to 450 Hz Single-phase) |
Rated input curren | 0.66A TYP. (At 100 VAC input) 0.4A TYP. (At 200 VAC input) |
Leakage current | 0.5 mA Max. (At 100 VAC input) 1.0 mA Max. (At 200 VAC input) |
Inrush current | 14 A TYP. (At 100 VAC input (For cold start at 25 CEL)) 28 A TYP. (At 200 VAC input (For cold start at 25 CEL)) |
Output voltage | 24 VDC |
Output voltage variable range | -10 to +15 % (With V. ADJ) (The output voltage may increase beyond the allowable voltage range (up to +15% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.) |
Ripple | 2%(p-p) Max. (Under the rated I/O conditions.) 150mV Max. (Under the rated I/O conditions.) |
Static input variation influence | 0.5% Max. At 85 to 264 VAC input, 100% load |
Static load variation influence | 1.5% Max. Output voltage: 24 V, at rated input, 0 to 100% load |
Ambient temperature variation influence | 0.05 %/CEL Max. |
Rated output current | 1.3 A |
Start up time | 560 ms TYP. (100 VAC input) 400 ms TYP. (200 VAC input) |
Hold time | 31ms TYP. (100 VAC input) 140ms TYP. (200 VAC input) |
Overload protection | 105% to 160% of the rated output current Inverted L voltage drop, Intermittent operation, Automatic reset |
Overvoltage protection | Operated at 130% Min. of the rated output voltage, Shut-off Resetting: Reset the power by turning it back (OFF time: at least 3 min) |
Overheat protection | No |
Maintenance forecast monitor output | No |
Total run time monitor output | No |
Undervoltage alarm output | No |
Power failure alarm output | No |
Parallel operation | No (However, backup operation is possible; external diodes required.) |
N+1 redundant system | - |
Series operation | Yes (Up to 2 Power Supplies with external diode) |
Remote sensing function | No |
Dielectric strength | Between all inputs and all outputs: 3 kVAC for 1 min (Detection current: 20 mA) Between all inputs and PE terminals: 2 kVAC for 1 min (Detection current: 20 mA) Between all outputs and PE terminals: 1 kVAC for 1 min (Detection current: 20 mA) |
Insulation resistance | Between all outputs and all inputs/ PE terminals: 100 MOhm Min. (at 500 VDC) |
Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s**2, in each 6 directions 3 times |
Output indicator | Yes (color: green) |
Heat radiation | Natural air-cooling |
Construction | Covered type |
Terminal type | Screw terminal |
Mounting type | DIN Rail mounting type |
Weight (Main) | Approx. 180 g |
Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.
As of October 10, 2016
As of October 10, 2016
Caution: All units are in millimeters unless otherwise indicated.
As of October 10, 2016
As of October 10, 2016
Block diagram
As of October 10, 2016
As of October 10, 2016
As of October 10, 2016