Switch Mode Power Supply (15/30/60/120/240/480-W Models)
Power rating |
240 W |
---|---|
Rated input voltage |
100 to 240 VAC |
Output voltage |
48 VDC |
Construction |
Covered type |
Terminal type |
Rod terminals |
Structure |
Screw terminals |
Mounting type |
Front-mounting type Side-mounting type DIN Rail mounting type |
As of October 10, 2016
Power rating | 240 W |
---|---|
Efficiency | 90% TYP.(At 100 VAC input) 92% TYP.(At 200 VAC input) |
Rated input voltage | 100 to 240 VAC |
Allowable input voltage variable range | 85 to 264 VAC 90 to 350 VDC |
Note at DC input | The following safety standards apply to a DC input: UL 60950-1, cUR (CSA C22.2 No. 60950-1), EN 50178, EN 60950-1, and Lloyd's. For a DC input, safety is ensured by an external fuse. Select an external fuse the meets the following conditions. S8VK-G240: 350 VDC min, 8 A |
Frequency | 50/60 Hz(47 to 450 Hz |
Rated input curren | 2.8A TYP. (At 100 VAC input) 1.5A TYP. (At 200 VAC input) |
Power factor | 0.9 Min. |
Leakage current | 0.5 mA Max. (At 100 VAC input) 1.0 mA Max. (At 200 VAC input) |
Inrush current | 16 A TYP. (At 100 VAC input (For cold start at 25 CEL)) 32 A TYP. (At 200 VAC input (For cold start at 25 CEL)) |
Output voltage | 48 VDC |
Output voltage variable range | -10 to +15 % (With V. ADJ) (The output voltage may increase beyond the allowable voltage range (up to +15% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.) |
Ripple | 350mV(p-p) Max. (at 20 MHz (Typical)) |
Static input variation influence | 0.4% Max. At rated output voltage and the rated output current |
Static load variation influence | 0.8% Max. At rated output voltage and the rated output current, maximum of the fluctuation of the output voltage when changing input voltage slowly at the reach of the permission input voltage |
Ambient temperature variation influence | 0.05 %/CEL Max. |
Rated output current | 5 A / 6 A (Peak current) |
Start up time | 300 ms TYP. (100 VAC input) 300 ms TYP. (200 VAC input) |
Hold time | 40ms TYP. (100 VAC input) 40ms TYP. (200 VAC input) |
Overload protection | 121% Min. of the rated output current Automatic reset |
Overvoltage protection | Operated at 130% Min. of the rated output voltage, Shut-off Resetting: Reset the power by turning it back (OFF time: at least 3 min) |
Parallel operation | Yes (Up to 2 Power Supplies) |
Series operation | Yes (Up to 2 Power Supplies with external diode) |
Dielectric strength | Between all inputs and all outputs: 3 kVAC for 1 min (Cut-off current: 20 mA) Between all inputs and PE terminals: 2 kVAC for 1 min (Cut-off current: 20 mA) Between all outputs and PE terminals: 1 kVAC for 1 min (Cut-off current: 20 mA) |
Insulation resistance | Between all outputs and all inputs/ PE terminals: 100 MOhm Min. (at 500 VDC) |
Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s**2, in each 6 directions 3 times |
Output indicator | Yes (color: green, lighting from 80% to 90% or more of rated voltage) |
Construction | Covered type |
Terminal type | Rod terminals |
Structure | Screw terminals |
Mounting type | Front-mounting type Side-mounting type DIN Rail mounting type |
Weight (Main) | Approx. 900 g |
Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.
As of October 10, 2016
As of October 10, 2016
Caution: All units are in millimeters unless otherwise indicated.
As of October 10, 2016
As of October 10, 2016
Block diagram
As of October 10, 2016
As of October 10, 2016
As of October 10, 2016
As of October 10, 2016
As of October 10, 2016
As of October 10, 2016
Mounting hole dimension
As of October 10, 2016
about this Product