Switch Mode Power Supply
Power rating |
30 W |
---|---|
Rated input voltage |
100 to 240 VAC |
Output voltage |
12 VDC |
Heat radiation |
Natural air-cooling |
Construction |
Covered type |
Structure |
Screw terminals |
Mounting type |
DIN Rail mounting type |
As of October 10, 2016
Power rating | 30 W |
---|---|
Efficiency | 73% TYP.(At rated input, 100% load) |
Rated input voltage | 100 to 240 VAC |
Allowable input voltage variable range | 85 to 264 VAC 80 to 370 VDC |
Note at DC input | The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 VAC (85 to 264 VAC). |
Frequency | 50/60 Hz(47 to 63 Hz Single-phase) |
Rated input curren | 0.7A Max. (At 100 VAC input) 0.4A Max. (At 200 VAC input) |
Power factor | 0.8 Min. (At rated input, 100% load) |
Leakage current | 0.35 mA Max. (At 100 VAC input) 0.7 mA Max. (At 240 VAC input) |
Inrush current | 17.5 A Max. (At 100 VAC input (For cold start at 25 CEL)) 35 A Max. (At 200 VAC input (For cold start at 25 CEL)) |
Output voltage | 12 VDC |
Output voltage variable range | -10 to +10 % (With V. ADJ) (The output voltage may increase beyond the allowable voltage range (up to +10% of the rated voltage) depending on the operation of the output voltage adjuster (V.ADJ). When adjusting the output voltage, check the output voltage of the Power Supply and be sure that the load is not damaged.) |
Ripple | 2%(p-p) Max. (Under the rated I/O conditions.) |
Static input variation influence | 0.5% Max. At 85 to 264 VAC input, 100% load |
Static load variation influence | 5% Max. Single operation, 0 to 100% load 2% Max. Single operation, 10 to 100% load 5.5% Max. Parallel operation, 0 to 100% load 3% Max. Parallel operation, 10 to 100% load |
Ambient temperature variation influence | 0.05 %/CEL Max. |
Rated output current | 2.5 A |
Start up time | 1000 ms Max. (100/200 VAC, rated input) |
Hold time | 20 ms Min. (100/200 VAC, rated input) |
Overload protection | 105% to 140% of the rated output current (Single operation), 100% to 140% of the rated output current (Parallel operation) Inverted L voltage drop, Automatic reset |
Overvoltage protection | Operated at 115 to 145 % of the rated output voltage, Shut-off Resetting: Reset the power by turning it back (OFF time: at least 1 min) |
Maintenance forecast monitor output | No |
Total run time monitor output | No |
Undervoltage alarm output | Yes (open collector output), 30 VDC Max., 50 mA Max. |
Parallel operation | Yes (Up to 4 Blocks) |
N+1 redundant system | Yes (Up to 5 Blocks) |
Series operation | Yes |
Dielectric strength | Between all inputs and all outputs: 3 kVAC for 1 min (Detection current: 20 mA) Between all inputs and all outputs: 2 kVAC for 1 min (Detection current: 20 mA) Between all inputs and all outputs: 1 kVAC for 1 min (Detection current: 20 mA) |
Insulation resistance | Between all outputs and all inputs/ PE terminals: 100 MOhm Min. (at 500 VDC) |
Vibration resistance | 10 to 55 Hz, 0.375 mm single amplitude in each 3 directions for 2 hours |
Shock resistance | 150 m/s**2, in each 6 directions 3 times |
Output indicator | Yes (color: green) |
Heat radiation | Natural air-cooling |
Construction | Covered type |
Structure | Screw terminals |
Mounting type | DIN Rail mounting type |
Weight (Main) | Approx. 450 g |
Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.
As of October 10, 2016
about this Product