IO-Link Photoelectric Sensor
Sensing method |
Retro-reflective with M.S.R. function |
---|---|
Sensing distance |
100 mm to 4 m (When using the E39-R1S) 100 mm to 3 m (When using the E39-R1) |
Light source |
Red LED (Emission wave length: 660 nm) |
Connection method |
Pre-wired models (Cable length: 2 m) |
As of March 3, 2017
Shape | Square type |
---|---|
Sensing method | Retro-reflective with M.S.R. function |
Sensing distance | 100 mm to 4 m (When using the E39-R1S) 100 mm to 3 m (When using the E39-R1) |
Standard sensing object | Opaque 75 mm dia. min. |
Directional angle | 2 to 10 DEG |
Light source | Red LED (Emission wave length: 660 nm) |
Power supply voltage | 10 to 30 VDC (ripple (p-p) 10% included) |
Current consumption | 30 mA max. |
Control output | PNP open collector output 30 VDC max. Load current: 100 mA max. Residual voltage: 1 V max. (Load current Less than 10mA)/Residual voltage: 2 V max. (Load current: 10 to 100 mA) |
Communications | IO-Link Ver1.1 Transmission speed: COM3 (230.4 kbps) Data length: PD size: 2 bytes, OD size: 1 byte (M-sequence type: TYPE_2_2) Minimum cycle time: 1 ms |
Operation mode | Light-ON/Dark-ON selectable |
Protective circuit | Output short-circuit protection Output reverse polarity protection Power supply reverse polarity protection Mutual interference prevention |
Response time | 1 ms max. |
Sensitivity setting | Sensitivity adjuster / IO-Link communications |
Ambient illuminance | Incandescent lamp: 3000 lux max., Sunlight: 10000 lux max. |
Ambient temperature (Operating) | -25 to 55 ℃ (with no icing or condensation) |
Ambient temperature (Storage) | -40 to 70 ℃ (with no icing or condensation) |
Ambient humidity | Operating: 35 to 85% Storage: 35 to 95% (with no icing or condensation) |
Insulation resistance | 20 MΩ min. at 500 VDC |
Dielectric strength | 1000 VAC at 50/60 Hz for 1 min |
Vibration resistance | 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions |
Shock resistance | 500 m/s**2 for 3 times each in X, Y, and Z directions |
Degree of protection | IEC: IP67 |
Connection method | Pre-wired models (Cable length: 2 m) |
Indicator | Standard I/O mode (SIO mode): Operation indicator (orange, lit) and stability indicator (green, lit) IO-Link mode: Operation indicator (orange, lit) and communication indicator (green, blinking at 1 s intervals) |
Weight (packed state) | Approx. 65 g |
Material | Case: PBT Lens: Methacrylate resin Display: Denatured Polyarylate |
Accessories | Instruction manual |
As of March 3, 2017
As of March 3, 2017
As of March 3, 2017
As of March 3, 2017
As of March 3, 2017
Series