IO-Link Proximity Sensor (Spatter-resistant Models)
Sensing head size |
M12 |
---|---|
Type |
Shielded |
Sensing method |
Inductive type |
Sensing distance |
3 mm ±10% |
Setting distance |
0 to 2.4 mm |
Operation mode |
NO/NC selectable |
As of August 8, 2016
Type | Shielded |
---|---|
Sensing method | Inductive type |
Sensing distance | 3 mm ±10% |
Setting distance | 0 to 2.4 mm |
Differential distance | 10% max. of sensing distance |
Sensing object | Ferrous metal (Sensitivity lowers with non-ferrous metals.) |
Standard sensing object | Iron 12 x 12 x 1 mm |
Power supply voltage | 10 to 30 VDC ripple(p-p) 10% included |
Current consumption | 20 mA max. |
Control output (Output type) | PNP DC 3-wire models |
Control output (Switching capacity) | 100 mA |
Control output (Residual voltage) | 20 V max.(Load current 100 mA with cable length of 2 m) |
Communications | IO-Link Ver1.1 Transmission speed: COM2 (38.4 kbps) Data length: PD size: 2 bytes, OD size: 1 byte (M-sequence type: TYPE_2_2) Minimum cycle time: 2.3 ms |
Indicator | Operation indicator (orange, lit) and stability indicator (green, lit) (Standard I/O mode (SIO mode)) Operation indicator (orange, lit) and communication indicator (green, blinking at 1 s intervals) (IO-Link mode) |
Operation mode | NO/NC selectable |
Self-diagnostic output | Equipped |
Protective circuit | Surge suppressor Output short-cut protection Output reverse polarity protection Power supply reverse polarity protection |
Ambient temperature | Operating: -25 to 70 ℃ Storage: -25 to 70 ℃ |
Ambient humidity | Operating: 35 to 95% RH Storage: 35 to 95% RH |
Temperature influence | ±10% max. of sensing distance in temperature range of -25 to +70 ℃ (As the basis for sensing distance of 23 ℃) |
Voltage influence | ±1% max. of sensing distance in rated voltage range ±15%. (As the basis for sensing distance at standard power voltage) |
Insulation resistance | Between charged parts and the case: 50 MΩ min. at 500 VDC |
Dielectric strength | Between charged parts and the case: 1000 VAC 50/60 Hz for 1 min |
Vibration resistance | 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions |
Shock resistance | 1000 m/s**2 for 10 times each in X, Y, and Z directions |
Degree of protection | IEC60529: IP67 Company standard: Oil-proof |
Connection method | Pre-wired models (Cable length: 2 m) |
Material (case) | Fluoride resin coating (base:brass) |
Material (sensing surface) | Fluoride resin |
Material (clamping nuts) | Fluoride resin coating (base: brass) |
Material (toothed washer) | Iron zinc plating |
Accessories | Instruction manual |
As of August 8, 2016
As of August 8, 2016
As of August 8, 2016
As of August 8, 2016
As of August 8, 2016
As of August 8, 2016
As of August 8, 2016
Series
about this Product